A. Shutdown Procedure
Turn the boiler off at the on/off power switch. Wait for the combustion
blower to stop, so all latent combustion gases are purged from the
system. This could take a maximum of 5 minutes.
B. Failure to Operate
Should the burner fail to light, the control will perform four more
ignition trials prior to entering a lockout state. Note that each
subsequent ignition trial will not occur immediately. After a failed
ignition trial, the blower must run for approximately 5 seconds to
purge the system.
If the burner lights during any one of these five ignition trails, normal
operation will resume.
If the burner does not light after the fifth ignition trial, the control will
enter a lockout state.
This lockout state indicates that a problem exists with the boiler, the
controls, or the gas supply.
Under such circumstances, a qualified service technician should be
contacted immediately to properly service the boiler and correct the
problem. If a technician is not available, press a button on the display
to wake it. Then press the RESET button to remove the lockout state so
additional trials for ignition can be performed.
If the RESET key is not pressed (error code 501 or 503), the boiler will
reset automatically after an hour.
C. Important
WARNING
It is extremely important that whenever work is performed on the
plumbing system that either:
The appliance is powered off, and,
The area that is being worked on is valved off and isolated.
Failure to take these measures could result in a dry-firing
condition, explosion or fire, substantial property damage, severe
personal injury, or death.
Part 1 - General Safety Information
Outdoor Sensor
Outside
Resistance
Temperature
(ohms)
o
(
F)
-22
178605
-13
132045
-4
98438
5
73995
14
56079
23
42846
32
32997
41
25609
50
20027
59
15777
68
12517
77
10000
86
8042
95
6510
104
5302
113
4343
Table 36 - Sensor Temperature Resistance

Part 16 - Shutdown

Supply/Return Temperature Sensors
Tank Sensor
DHW Outlet Sensor
Water Temp.
Resistance (Ohms)
o
(
F)
32
27219
41
22021
50
17926
59
14674
68
12081
77
10000
86
8315
95
6948
104
5834
113
4917
122
4161
131
3535
140
3014
149
2586
158
2228
167
1925
176
1669
185
1452
194
1268
202
1110
212
974