NTI - TRINITY Ti
INSTALLATION AND OPERATION INSTRUCTIONS
Ti100-200 Boilers and Ti150-200 Combi Models
VERSION DATE: 2013-05-21

TABLE OF CONTENTS

1.0 SPECIFICATIONS ........................................................................................... 4
2.0 BOILER LOCATION ....................................................................................... 5
3.0 GENERAL VENTING ...................................................................................... 6
4.0 VENT/AIR-INTAKE TERMINATION CLEARANCES ............................ 15
5.0 CONDENSATE DRAIN ................................................................................. 19
6.0 INSTALLING GAS PIPING .......................................................................... 20
7.0 LIGHTING THE APPLIANCE ..................................................................... 21
8.0 GAS VALVE AND BURNER SET-UP ......................................................... 23
9.0 BOILER AND HEATING SYSTEM PIPING .............................................. 26
11.0 WIRING ........................................................................................................... 36
12.0 SENTRY 2100 CONTROLLER ..................................................................... 42
13.0 TROUBLESHOOTING .................................................................................. 46
14.0 SEQUENCE OF OPERATION ..................................................................... 49
15.0 WIRING SCHEMATIC ................................................................................. 50
16.0 INSTALLATION CHECKLIST .................................................................... 51
17.0 ANNUAL MAINTENANCE AND INSPECTION ....................................... 52
18.0 PARTS LIST .................................................................................................... 54
HAZARD SYMBOL DEFINITIONS
Danger Sign: Indicates a hazardous situation which, if not avoided, will
result in serious injury or death.
Warning Sign: Indicates a hazardous situation which, if not avoided, could
result in serious injury or death.
Caution Sign plus Safety Alert Symbol: Indicates a hazardous situation
which, if not avoided, could result in minor or moderate injury.
Caution Sign without Safety Alert Symbol: Indicates a hazardous situation
which, if not avoided, could result in property damage.
Notice Sign: Indicates a hazardous situation which, if not avoided could
result in property damage.
US Models
H
NTI # 82419

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Ti100-200 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for NTI Ti100-200

  • Page 1: Table Of Contents

    NTI – TRINITY Ti INSTALLATION AND OPERATION INSTRUCTIONS Ti100-200 Boilers and Ti150-200 Combi Models VERSION DATE: 2013-05-21 TABLE OF CONTENTS 1.0 SPECIFICATIONS ................... 4 2.0 BOILER LOCATION ..................5 3.0 GENERAL VENTING ..................6 4.0 VENT/AIR-INTAKE TERMINATION CLEARANCES ......15 5.0 CONDENSATE DRAIN .................
  • Page 2 General Installation Requirements The installation of the NTI Trinity Ti gas boiler must conform to the requirements of this manual, your local authority, and the National Fuel Gas Code ANSI Z223.1 and or CAN/CGA B149 Installation Codes. Where required by the Authority Having Jurisdiction, the installation must conform to the standard for “Controls and Safety Devices for Automatically Fired Boilers...
  • Page 3 Installation and Operation Instructions │Trinity Ti Series Energy Saving Feature - This boiler is equipped with a feature that saves energy by reducing the boiler water temperature as the heating load decreases. This feature is equipped with an override which is provided primarily to permit the use of an external energy management system that serves the same function.
  • Page 4: Specifications

    Trinity │Installation and Operation Instructions Ti Series 1.0 SPECIFICATIONS Table 1-1 Specifications DESCRIPTION Ti100 Ti150 Ti200 CSA Input Modulation 15,000 - 93,000 25,000 - 150,000 25,000 - 199,000 [4.4 – 29.3] btu/hr [kw] [7.3 - 44.0] [7.3 - 58.3] DOE Heating Capacity 84,000 136,000 181,000...
  • Page 5: Boiler Location

    Rear Flue/Water Pipe Minimum 24 [610] 12 [305] 12 [305] 9 [229] 1 [25] Trinity Ti100-200 Recommended 24 [610] 24 [610] 24 [610] 9 [229] 1 [25] Notes: 6” if surface is removable allowing 24” [610 mm] clearance (i.e. closet installation). See “Appliance Ventilation Air Openings”...
  • Page 6: General Venting

    Trinity │Installation and Operation Instructions Ti Series 3.0 GENERAL VENTING The Trinity Ti is a “Direct Vent” appliance requiring a “Special Venting System” designed for pressurized venting. Both the Vent and Air-Intake piping must be piped to the outdoors, using the vent material and rules outlined in this section. Under no conditions may this unit vent gases into a masonry chimney, unless it is vacant, and utilizes the approved venting material and rules described in this section.
  • Page 7 In Canada, the first 3 ft (915 mm) of vent piping must be readily accessible for inspection. Table 3-2 Mandatory Vent Pipe Transition Piece Model No. CPVC Vent Pipe Size CPVC Transition Vent Pipe Length Full Insertion Depth 3” Minimum 5” [127 mm] 2-7/8” [73 mm] Trinity Ti100-200...
  • Page 8 Trinity │Installation and Operation Instructions Ti Series Vent/Air-Intake Pipe Material Table 3-3 Acceptable Vent and Air-Intake Pipe Material Installation Standards 2, 3 Items Materials United States Canada PVC - DWV ANSI/ASTM D2265 All Vent and Air-Intake materials installed on gas PVC Schedule 40 ANSI/ASTM D1785 Vent Piping...
  • Page 9 See Figs 3-2(b) and 3-3(b). Optional Termination Kits Kits certified with the Trinity Ti are listed in Table 3-5 and available from IPEX and/or NTI. For more information on System 636 │...
  • Page 10 Trinity │Installation and Operation Instructions Ti Series Concentric Venting Options Figure 3-2(a) Figure 3-2(b) Concentric Side Wall Termination (Optional Kit) Concentric Roof Termination (Optional Kit) Two-Pipe Venting Options Figure 3-3(a) Figure 3-3(b) Two-Pipe Side Wall Termination Two-Pipe Roof Termination...
  • Page 11 Installation and Operation Instructions │Trinity Ti Series Labeling and Identification – Roof Top Terminations Figure 3-4(a) Figure 3-4(b) Two-Pipe Roof Top Termination Concentric Vent Roof Top Termination Two-pipe terminations typically penetrate the roof surface. To prevent water leakage, install adequate roof weather seal An alternative is to use an existing chimney as a chase way.
  • Page 12 Trinity │Installation and Operation Instructions Ti Series Labeling and Identification – Two Pipe Side Wall Labeling and Identification – Optional Kit Figure 3-6 Figure 3-7 Two-Pipe Side Wall Termination Concentric Vent Termination Kit Gas Vent Directly Below Air Inlet Pipe Keep Free of Obstructions Exhaust End Cap...
  • Page 13 Combustion air containing chemicals such as chloride, fluoride, bromine or iodine or dust and debris will cause corrosion damage of the heat exchanger voiding your NTI warranty. Refer to Table 3-1 for a list of corrosive products and contaminants sources to avoid.
  • Page 14 The Vent/Air-intake piping MUST be secured to the side of the building above grade, as shown, to provide rigidity. Mounting Bracket NTI Provides a mounting bracket PN. 82075 for securing the exhaust pipes. Ensure that the Vent/Air-Intake clearances are maintained, see Section 4.0 for details. Figure 3-10...
  • Page 15: Vent/Air-Intake Termination Clearances

    Installation and Operation Instructions │Trinity Ti Series 4.0 VENT/AIR-INTAKE TERMINATION CLEARANCES The quick reference table below is to be read in conjunction with the numbered notes as indicated, Figures 4-1 through 4-6, and the Venting Rules and Guidelines in Section 3.0. The instructions detailed in this section are a combination of Trinity Ti specific and National Gas Code restrictions.
  • Page 16 Trinity │Installation and Operation Instructions Ti Series Figure 4-1 Termination Clearances Quick Reference Diagram Illustrations of Termination Clearances Figure 4-2 Side Wall Termination - Clearances Above Grade Clearances “F” and “G” Canada – Minimum 3 ft [915 mm] The US – Minimum 1 ft [305 mm] Two-Pipe Termination Clearance “Q”...
  • Page 17 Installation and Operation Instructions │Trinity Ti Series Figure 4-3 Typical Figure 4-4 Two-Pipe Side Wall Clearances Concentric Vent Side Wall Clearances Horizontal Separation Exhaust from 4-12” [102 mm – 305 mm] or boiler greater than 36” [915 mm] Combustion From boiler Air-Inlet exhaust To boiler...
  • Page 18 Trinity │Installation and Operation Instructions Ti Series Extra precaution must be taken to adequately support the weight of the Vent/Air-Intake piping in applications using roof-top terminations. Failure to follow these instructions may result in venting or boiler component failure resulting in flue gas spillage leading to property damage, serious injury or death. Under no circumstances may an existing chimney or chase-way be used to vent or provide combustion intake air to a Trinity Ti.
  • Page 19: Condensate Drain

    Installation and Operation Instructions │Trinity Ti Series 5.0 CONDENSATE DRAIN This unit produces water as a product of combustion. Much of this water condenses on the heat exchanger and in the venting system. All exhaust piping must be on a slope back to the boiler ¼” per linear foot of vent. Steps must be taken to ensure that condensate does not collect in the venting system.
  • Page 20: Installing Gas Piping

    Ensure that:  The gas line connection to the appliance does not apply any weight to the gas valve. NTI recommends using approved flexible gas piping (if acceptable by local codes) to connect the appliance to the gas supply (See Figure 6-1 for details).
  • Page 21: Lighting The Appliance

    Installation and Operation Instructions │Trinity Ti Series 7.0 LIGHTING THE APPLIANCE Before Start-up refer to Mandatory Pre-commissioning Procedure for Plastic Venting in Section 3.0. Failure to follow these instructions can result in explosions, injury or death. Prior to turning the gas supply on and lighting the appliance, ensure all aspects of the installation are complete and in conformance with the instructions provided in this manual, including the Vent/Air- Intake, Condensate Drain, and System Water Piping.
  • Page 22 Once you have successfully activated the flame safety system, replace the wire on the flame sensor, and reconfirm proper lighting. If the unit fails to light consistently and smoothly, contact NTI for assistance at 1-800-688-2575. Never allow the appliance to continue to operate if the ignition or operation of the burner is rough or erratic.
  • Page 23: Gas Valve And Burner Set-Up

    Installation and Operation Instructions │Trinity Ti Series 8.0 GAS VALVE AND BURNER SET-UP Set-up of the Trinity Ti gas valve must be performed by a licensed Gas Technician. Failure to perform the set-up correctly may result in incorrect operation, component failure, property damage, serious injury or death.
  • Page 24 The Throttle/Input screw for models Ti100-200 is a multiple turn valve. Fully open to close is approximately 17 turns. Typical adjustment for Natural Gas is 0-1 full turns in or out from its factory position.
  • Page 25 Operate the unit at the minimum Gas Input Value (Table 8-2). Ensure the combustion remains smooth and CO and CO remain within the limits (Table 8-1). If not, do not adjust further, contact NTI for assistance. Maximum Modulation Rate – The Trinity Ti boiler is equipped with an electronic burner control that will modulate the firing rate to match the demand placed on the unit.
  • Page 26: Boiler And Heating System Piping

    For retrofits, all system piping including radiators, must be cleand of all build-up including sludge and scale. All systems, old and new, must be cleaned to remove flux, grease and carbon residue. NTI recommends cleaning the boiler system with “Fernox F3 Cleaner”.
  • Page 27 Installation and Operation Instructions │Trinity Ti Series Near Boiler Plumbing Pressure Relief Valve - A 30PSI Pressure Relief Valve is factory supplied with all boilers. Since all Trinity Ti boilers, excluding Ti100’s and Ti150’s sold in Canada (MAWP=30PSI), have a maximum operating pressure of 145PSI, a pressure relief valve with a higher discharge pressure rating (up to the MAWP of the boiler) may be used as long as the relieving capacity is in excess of the maximum input capacity of the boiler, see boiler rating plate.
  • Page 28 Trinity │Installation and Operation Instructions Ti Series Figure 9-1(d) Ti150 Combi Canada Boiler Inlet Relief Valve Port DHW Outlet Boiler Outlet DHW Inlet Combi Return Combi Return Manifold PN: 82470-1 Boiler System Plumbing The Trinity Ti boiler uses a low mass heat exchanger that requires a minimum rate of forced water circulation any time the burner is operating (See Table 9-3 for minimum flow rates).
  • Page 29 LWCO must be at least 6” above the top of the boiler.  Flow Switch must be installed in a 1” diameter line directly in series with the boiler at all times. NTI recommends a “McDonnell & Miller” model number “FS8-W”.
  • Page 30 Trinity │Installation and Operation Instructions Ti Series Figure 9-2 Boiler System Plumbing (non-Combi) NOTICE: See Figures 9-1(a) and (b) for identification of plumbing connections.
  • Page 31 Installation and Operation Instructions │Trinity Ti Series Figure 9-3 Boiler System Plumbing (Combi) NOTICE: See Figure 9-1(c) and (d) for identification of plumbing connections. NOTICE: Do not install zone or check valves between the inlet of PUMP C1 and the expansion tank.
  • Page 32: Combi Boiler Dhw Plumbing And Operation

    “LO” setting (See Section 12.0). The LO setting is accessed via the menu in the Sentry 2100 controller, and should be set at a value sufficient to heat the potable water, i.e. 150-165ºF. NTI provides a Thermostatic Mixing Valve adjustable from 100 to 145°F;...
  • Page 33 Installation and Operation Instructions │Trinity Ti Series Cleaning – Brazed plate heat exchangers operate with high turbulence flow, even at low flow rates. This high turbulence keeps small particles in suspension minimizing fouling and scaling. However, in some applications the fouling tendency can be very high, e.g.
  • Page 34 Combi and enters the inlet fitting of the storage tank. In lieu of the DHW flow switch, NTI recommends using an isolation relay activated with the potable re- circulating pump. The isolated end-switch of the relay would be wired to the boiler’s A-C terminals in...
  • Page 35 Installation and Operation Instructions │Trinity Ti Series Figure 10-1 Combi DHW Piping (no Storage) NOTICE: Install flow switch in the vertical position with the flow entering the bottom. Figure 10-2 Combi DHW Piping (w/ Storage)
  • Page 36: Wiring

    Trinity │Installation and Operation Instructions Ti Series 11.0 WIRING All wiring must be in accordance with the Canadian Electrical code, CSA C22.2 and any applicable local codes. Ensure that the wiring complies with this manual. The boiler must be electrically grounded in accordance with the National Electrical Code ANSI/NFPA 70, local codes, and/or the Canadian Electrical Code CSA C22.1.
  • Page 37 Installation and Operation Instructions │Trinity Ti Series Simplified Wiring Connections Sensor DHW Aquastat / or Combi Flow Switch Table 11-1 Line Voltage Field Connections Connection Color Description Location for connecting line voltage of the power supply. Note; most installation codes require Black (120VAC) the installation of a service switch to break line voltage to the appliance.
  • Page 38 Trinity │Installation and Operation Instructions Ti Series Advanced Wiring Systems Figure 11-3 Zone Valve System – No Zone Controller Legend Blue P1- Primary Pump P3 - Secondary pump P2- Indirect pump, or CB - Trinity Control box Combi Valve *R – 120V Relay Coil *R1 - Relay Contact * Only required with Combi boiler.
  • Page 39 Installation and Operation Instructions │Trinity Ti Series Figure 11-4 Zone Valve System – w/Zone Controller LEGEND: P1 – Primary Pump CB – Trinity Control Box P2 – Indirect Pump, or Combi Valve P3 – Secondary Pump *R – 120V Relay Coil *R1 –...
  • Page 40 Trinity │Installation and Operation Instructions Ti Series Figure 11-5 Zone Circulator Systems Legend P1 - Primary Pump P2 - Indirect pump or Combi Valve CB - Trinity Control box Indirect Aqua- stat or Combi flow switch Zone Circulator System – w/Zone Controller Figure 11-5 illustrates a typical wiring configuration required for a heating system using zone circulators with a zone circulator controller (Example shows a Taco model SR504).
  • Page 41 Installation and Operation Instructions │Trinity Ti Series Figure 11-6 Zone Circulator System w/Multiple Temperatures Indirect Aqua-stat, or combi flow switch Loop 1 (Hi Temp.) Thermostat, or manifold end switch Loop 2 (Lo Temp.) Thermostat, or manifold end switch Legend P1- Primary Pump ZP- Zone Pump P2- Indirect pump or 3-way Valve in Combi BS.- Strap on boiler sensor...
  • Page 42: Sentry 2100 Controller

    Ti Series 12.0 SENTRY 2100 CONTROLLER The Sentry controller used on Ti400 is different then the Sentry controller used on Ti100-200 models. The T4.1 controller can only be used on Ti400’s, while the T2.2 controller can only be used on Ti100-Ti200’s) The Sentry controller is the central controller for the Trinity boiler.
  • Page 43 Installation and Operation Instructions │Trinity Ti Series Sentry 2100 Operation The Trinity boiler employs a pneumatic modulation system. This modulation system increases or decreases the speed of the blower to meet the demand for heating. The gas valve senses this change in blower pressure, and introduces the required amount of gas to ensure correct combustion.
  • Page 44: Setting Sentry 2100

    Trinity │Installation and Operation Instructions Ti Series Setting the Sentry 2100   Programming is accomplished by a series of three push buttons located on the bottom side of the control. (Function, ). To  enter the programming mode, press the function key once. To scroll through the various menu options depress until the desired ...
  • Page 45 Installation and Operation Instructions │Trinity Ti Series Outdoor Sensor (10K) To fully take advantage of the energy saving features of the Trinity boiler, it is necessary to install the outdoor sensor provided. Install the sensor preferably on the north, or coldest side of the building, not within 10 feet of the discharge of the gas vent outlet, or other sources of heat.
  • Page 46: Troubleshooting

    “24V Limit Error” temperature. If operation is unsuccessful and the error reoccurs continue to step 2. Ti100-200’s are equipped with a low water pressure switch on the boiler Sentry has sensed a lack of On Display 24V on the outlet of the return that requires a minimum of 10PSI to complete the 24VAC Sentry burner relay (B1).
  • Page 47 Boiler may be plugging-up with scale or magnetite, clean with Fernox Boiler bangs while burner is running DS-40 Descaler and Cleaner (NTI PN: 83450). or hisses indicates insufficient flow If glycol is being used the concentration may be to high, recommend using a concentration lower then 35%.
  • Page 48 (weight of line), or horizontally (misaligned connection) Reset power, if display comes back on contact NTI for assistance. Ensure 120VAC is being supplied to the boiler. Check the internal fuse in the Sentry – to access the internal fuse,...
  • Page 49: Sequence Of Operation

    Installation and Operation Instructions │Trinity Ti Series 14.0 SEQUENCE OF OPERATION The following is the normal sequence of operation for the trinity boiler. Trinity Sequence of operation 120v Power Displays version Boiler in Applied t2.0 or t4.0 standby mode Indirect thermostat Thermostat, End switch or flow switch closes A-C or relay closes T-C...
  • Page 50: Wiring Schematic

    Trinity │Installation and Operation Instructions Ti Series 15.0 WIRING SCHEMATIC...
  • Page 51: Installation Checklist

    Installation and Operation Instructions │Trinity Ti Series 16.0 INSTALLATION CHECKLIST Installation  1. If operating on Propane Gas, convert appliance using kit number 82650-1.  2. Install the Vent/Air-Intake piping in accordance with Section 4.0 of this manual. Ensure all joints are secured and cemented properly.
  • Page 52: Annual Maintenance And Inspection

     8. Listen for water flow noises indicating a drop in appliance water flow rate. Important - The hydronic system may need to be flushed to eliminate hard water scale (Use Fernox DS-40 Descaler, NTI PN: 83450). Combustion Chamber Cleaning Procedure Units operating with LP Gas or in an industrial environment will have to be cleaned a minimum of once per year.
  • Page 53 Installation and Operation Instructions │Trinity Ti Series Refractory Ceramic Fibers (RFC) Personal Protective Equipment Recommended - Read the following warnings and handling instructions carefully before commencing any service work in the combustion chamber. The insulating material on the inside of the burner door and at the back of the combustion chamber contain Refractory Ceramic Fibers and should not be handled without personal protective equipment.
  • Page 54: Parts List

    Rauscchert Flame Rod 82763 Composite Flue Box 11A 82764 Composite Flue Box Gasket 11B 82765 Composite Flue Outlet Gasket 11C 83291-1 Flue Adapter Assembly (Ti100-200) 82992 Manifold Limit, 1/4NPT(Ti100-150 ASME) 82596 Ti100-150 Heat Exchanger 83012 Ti100-150 ASME Heat Exchanger 82647...
  • Page 55 Installation and Operation Instructions │Trinity Ti Series Notes...
  • Page 56 NY Thermal Inc. 65 Drury Cove Road Saint John, NB E2H 2Z8 Canada Technical Assistance: 1-800-688-2575 Website: www.nythermal.com Fax: 1-506-432-1135...