Levelflex FMP53 PROFIBUS PA
2.
Turning securing clamp 90 ° counterclockwise and tighten the clamp with
2.5 Nm (1.84 lbf ft) again using the Allen key (3 mm).
7.3
Post-connection check
Is the device or cable undamaged (visual check)?
Do the cables comply with the requirements ?
Do the cables have adequate strain relief?
Are all cable glands installed, securely tightened and leak-tight?
Does the supply voltage match the specifications on the nameplate?
Is the terminal assignment correct?
If required: Has protective ground connection been established ?
If supply voltage is present, is the device ready for operation and do values appear on the display
module?
Are all housing covers installed and securely tightened?
Is the securing clamp tightened correctly?
8
Integration into a PROFIBUS network
8.1
Overview of the device database files (GSD)
Manufacturer ID
Ident number
Profile version
GSD file
GSD file version
Endress+Hauser
17 (0x11)
0x1558
3.02
Information and files under:
•
www.endress.com
•
www.profibus.org
Integration into a PROFIBUS network
29
Need help?
Do you have a question about the Levelflex FMP53 and is the answer not in the manual?