Commissioning via wizard

9
Commissioning via wizard
A wizard guiding the user through the initial setup is available in FieldCare and DeviceCare
1.
Connect the device to FieldCare or DeviceCare (for details refer to the "Operating
options" chapter of the Operating Instructions).
2.
Open the device in FieldCare or DeviceCare.
 The dashboard (home page) of the device appears:
1
"Commissioning" button calls up the wizard.
3.
Click on "Commissioning" to call up the wizard.
4.
Enter or select the appropriate value for each parameter. These values are immediately
written to the device.
5.
Click "Next" to switch to the next page.
6.
After finishing the last page, click "End of sequence" to close the wizard.
If the wizard is cancelled before all necessary parameters have been set, the device may
be in an undefined state. A reset to the default settings is recommended in this case.