Analog Output Wiring - Tecfluid FLOMID Series Instruction Manual

Sensor and converter
Hide thumbs Also See for FLOMID Series:
Table of Contents

Advertisement

These terminals correspond to an input that resets the value of the totalizer. A potential free
normally open push button can be connected. The push button contact must be a good
quality snap action switch to guarantee correct working at low voltages and reduce contact
bounce effects.
2.2.4

Analog output wiring

The analog output is galvanically isolated. It can be either active (which means that the
receiving device must be passive) or passive (which means that the receiver must supply the
power for the current loop). It is recommended to use a receptor with an input resistance of
less than 700 Ω to guarantee correct operation.
The configuration of the analog output mode (active or passive) is done by means of the
connection to the terminal strip. For active mode, terminals 11 and 12 are connected. For
passive mode, terminals 12 and 13 are connected.
NOTE: The analog output has protection against reversed polarity. Due to another
protection against over voltages, if a loop supply voltage of more than 32 V is connected the
converter may be damaged.
Terminal
1
Contact
2
Contact
Terminal
11
mA (positive, active output)
12
mA
13
mA (negative, passive output)
19