NetSure
-48 VDC Power System
Installation Instructions, IM582127000100 (Revision A, January 9, 2017)
Figure 10.
Installing an Optional Bullet Nose Type 6-Position GMT Distribution Fuse Block (P/N 549017)
Spec. No: 582127000100, 582127000103
Model No: 7100
1. Remove two lug terminal busbars for positions to be occupied
by GMT Fuse Block. Remove plastic busbar plugs first.
Plastic Busbar Plugs
2. Plug in GMT Fuse Block.
Part of P/N 549017
3. Connect supplied jumper from
GMT Fuse Block to Return Bar.
Torque to 75 in-lbs.
Part of P/N 549017
[14]
RTN Bar
Document Code: IM582127000100
Revision A, January 9, 2017