Emerson NetSure-48 VDC Power System Installation Instructions Manual page 16

Table of Contents

Advertisement

NetSure
-48 VDC Power System
Installation Instructions, IM582127000100 (Revision A, January 9, 2017)
Figure 6.
Battery Tray Battery Disconnect Circuit Breaker Alarm Wiring
Alarm Wiring to Battery Disconnect Circuit
Breakers when (1) to (3) Battery Trays are Used
Connect stripped end
to TB1 located on the
System Interface Board.
Spec. No: 582127000100, 582127000103
Model No: 7100
Yellow Alarm Wire
Harness, P/N 524384
To Power System
Torque to 60 in.-lbs.
using supplied
hardware.
To Power System
Torque to 60 in.-lbs.
using supplied
hardware.
To Power System
Torque to 60 in.-lbs.
using supplied
hardware.
Procedure
1.
Connect kit-supplied YELLOW jumper/alarm lead
(P/N 524384) to circuit breaker "C (Common)"
alarm terminals on ALL Battery Disconnect Circuit
Breakers. Connect remaining end to TB1 located on
the System Interface Board.
2.
There is NO connection to the circuit breaker
"NO (Normally Open)" alarm terminal.
3.
On ALL Battery Disconnect circuit breakers,
there should be a factory connected Jumper
connected from the bottom terminal on the circuit
breaker to the circuit breaker "NC (Normally Closed)"
alarm terminal.
To Battery
Torque to 60 in.-lbs.
using supplied
hardware.
3rd Battery Tray
Battery Disconnect
Circuit Breaker
(Side covers removed in illustration
to show wiring details.)
To Battery
Torque to 60 in.-lbs.
using supplied
hardware.
2nd Battery Tray
Battery Disconnect
Circuit Breaker
To Battery
Torque to 60 in.-lbs.
using supplied
hardware.
1st Battery Tray
Battery Disconnect
Circuit Breaker
[8]
Document Code: IM582127000100
Revision A, January 9, 2017

Advertisement

Table of Contents
loading

This manual is also suitable for:

7100582127000100582127000103

Table of Contents