Connecting Battery Tray Cables to the Battery Tray's Battery Disconnect Circuit Breaker
Procedure
1.
Connect battery tray cables labeled (-) to the battery disconnect circuit breaker located on each battery tray Refer to
2.
Rout the cables into the battery trays. The unconnected ends are connected to the battery strings in a later procedure.
Battery Tray Battery Disconnect Circuit Breaker Alarm Wiring
Procedure
1.
Connect alarm jumper P/N 524384 to the battery disconnect circuit breakers located on the battery trays by performing the
procedure detailed in
2.
Connect the stripped end of alarm jumper P/N 524384 to TB1 located on the System Interface Board. –48VDC is applied to the
alarm lead when the circuit breaker is in the OFF position. Refer to
Connecting Battery Temperature Probes
Procedure
Three battery temperature probes are provided. Refer also to "Temperature Probes" on page 23.
1.
Connect a temperature probe to the System Temp 1 input on the System Interface Board. Route this probe to the bottom
battery tray. Refer to
2.
Connect a temperature probe to the System Temp 2 input on the System Interface Board. Route this probe to the center
battery tray. Refer to
3.
Connect a temperature probe to the Temp 1 input on the IB2-1 interface board. Route this probe to the top battery tray. Refer
to
Figure
18.
4.
In the event there is excess length of the probe wires, coil the wires up and tie in a convenient location along the path of the
battery power cable.
Spec. No: 582127000100, 582127000103
Model No: 7100
Figure
6.
Figure
17.
Figure
17.
Figure
6. Refer also to
[7]
Figure
Figure
17.
Document Code: IM582127000100
Revision A, January 9, 2017
6.