Switching operations for disconnectable voltage transformers

Connecting voltage transformers with busbar 1
1
Initial situation
3
Switch the three-position disconnector to
CLOSED position (insert the operating lever for
the DISCONNECTING function and turn
180° clockwise).
Disconnecting voltage transformers from busbar 1
1
Initial situation
3
Switch the three-position disconnector to OPEN
position (insert the operating lever for
the DISCONNECTING function and turn
180° counter-clockwise).
2
Push the control gate to the left.
4
Remove the operating lever for
the DISCONNECTING function.
The control gate returns to its initial position.
2
Push the control gate to the left.
4
Remove the operating lever for
the DISCONNECTING function.
The control gate returns to its initial position.