Description; Features - Siemens 8DB10 Installation And Operating Instructions Manual

Extendable fixed-mounted circuit-breaker switchgear up to 40.5 kv
Table of Contents

Advertisement

Description

Typical uses
Insulating gas SF
Technology
Personal safety
Security of operation and
availability
Cost-efficiency
National approvals
Seismic withstand
capability (option)
10/214
Description
5

Features

Extendable fixed-mounted circuit-breaker switchgear of the 8DB10 series is mainly used in
transformer and distribution substations as well as for switching duties in industrial plants.
The panels are designed for rated voltages up to 40.5 kV and rated currents up to 2500 A. In
distribution systems up to 40.5 kV, a maximum short-circuit current of 40 kA is permissible.
Sulfur hexafluoride SF
6
the housing wall.
When several switchgear sections have to be delivered, the switchgear is delivered ex works
partly with SF
filling ready for service. To fill all gas compartments completely with SF
6
SF
gas and a filling device must be provided on site. If the switchgear is delivered as one
6
switchgear section (possible for switchgear assemblies comprising up to 4 panels),
the switchgear is delivered ex works completely with SF
The SF
filling is provided to last the total service life of the switchgear.
6
Filling quantity as per rating plate.
• Factory-assembled, type-tested and metal-enclosed switchgear for indoor installation
• Double busbar
• Single-pole metal enclosure
• Safe-to-touch connection and interconnection system for cables as well as for solid-
insulated and gas-insulated bars
• Complete switchgear interlocking system with logical mechanical interlocks
• Minimum fire load
• Primary part independent of environmental effects (pollution, humidity and small animals)
due to hermetically sealed enclosure
• Maintenance-free under normal ambient conditions according to IEC 62271-1 and
VDE 0671-1
8DB10 switchgear has obtained the following national approval:
• GOST R certificate
8DB10 switchgear can be upgraded for operation in regions at risk from earthquakes,
see the relevant order and delivery documents.
Revision 06 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • 864-5091.9
is used as insulating gas. SF
6
insulates live parts against
6
filling ready for service.
6
,