Siemens 8DB10 Installation And Operating Instructions Manual page 55

Extendable fixed-mounted circuit-breaker switchgear up to 40.5 kv
Table of Contents

Advertisement

Fig. 46:
Screwed floor fixing
Fig. 47:
Welded floor fixing
Fig. 48:
Fixing on double floor
864-5091.9 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • Revision 06
Siemens recommendation for the floor fixing
Upper edge of finished floor
Floor fixing plate (holder for profiles at a distance
≥ 1200 mm), see page 56, "Floor fixing plate"
C-profile CB 50 x 30, EN 10025, S235JR
• Hook-head bolt M16x35-4.6
• Washer R18, DIN 440/ISO 7094, S235JRG2C + L
• Hexagonal nut M16-8, DIN EN ISO 4032
Base frame of the switchgear
Min. 50 mm
Min. 90 mm
80 mm
Raw floor
Expansion dowel with hexagonal bolt and washer,
FAN 12/10
Floor finish
Upper edge of finished floor
Base frame of the switchgear
Welding in fixing opening of base frame
U-profile U80, DIN 1026
Floor fixing plate (holder for profiles at a distance
≥ 1200 mm), see page 56, "Floor fixing plate"
Min. 55 mm
Min. 90 mm
80 mm
Raw floor
Expansion dowel with hexagonal bolt and washer,
FAN 12/10
Floor finish
Upper edge of double floor
• Hexagonal bolt M10-8, DIN 931/933
• Washer 10.5-St, EN ISO 7093-1
• Hexagonal nut M10-8, DIN EN ISO 4032
Base frame of the switchgear
Substructure
Supporting profile (e.g. profile 70 x 40 x 2)
Floor plate (approx. 36 mm thick)
Installation
55/214

Advertisement

Table of Contents
loading