Description
Features
Voltage transformer types
Electrical data
Designation
Operating voltage kV
Rated voltage kV
Rated short-duration power-frequency
withstand voltage kV
Rated lightning impulse withstand voltage kV
Rated voltage factor
Standard
28/214
12
Current and voltage transformers
12.1
Voltage transformers
• According to IEC 60044-2
• Cast-resin insulated
• Inductive type
• Safe-to-touch due to metal enclosure
Fig. 12:
Voltage transformer installation (basic scheme)
①
Busbar voltage transformer 4MT3
②
Feeder voltage transformer 4MT7
(connection at panel connection housing)
Mounting locations
Type
Busbar
4MT3
4MU4
Panel connection
4MU3
4MT7
4MT3
3.3 to 23.0
24.0
65.0
125.0
Un / 8h = 1.9
Un / continuous = 1.2
IEC
GOST
GB
Revision 06 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • 864-5091.9
③
Voltage transformer 4MU4 with
three-position disconnector
④
Feeder voltage transformer 4MU3 (not in
the panel, connection via flexible cable with plug
size S2 at the panel connection housing, and
metal-enclosed voltage transformer)
Comment
optionally with three-position disconnector
external
directly pluggable
4MU4
4MT7
24.0 to 38.0
3.3 to 38.0
40.5
40.5
95.0
95.0
200.0
200.0
Un / 8h = 1.9
Un / 8h = 1.9
Un / continuous = 1.2
Un / continuous = 1.2
IEC
IEC
GOST
GOST
GB
GB
4MU3
3.3 to 38.0
40.5
95.0
200.0
Un / 8h = 1.9
Un / continuous = 1.2
IEC
GOST
GB