Siemens 8DB10 Installation And Operating Instructions Manual page 78

Extendable fixed-mounted circuit-breaker switchgear up to 40.5 kv
Table of Contents

Advertisement

Installation
Correcting contact
overlapping of
disconnector contacts
78/214
Fig. 73:
Disconnector coupling rod
➭ Undo the locknuts ② at the hexagonal sleeve of the disconnector coupling rod ① .
➭ Modify the length of the disconnector coupling rod by turning the hexagonal sleeve ① ,
so that the contact fingers are resting exactly on the fixed contact of the disconnector in
CLOSED position.
Fig. 74:
Example for correct and incorrect position of the contact fingers
on the fixed contact
➭ Verify proper contact overlapping after several switching operations with
the operating mechanism of the three-position disconnector.
➭ Tighten the locknuts ② again with a tightening torque of 20 Nm.
Revision 06 • INSTALLATION AND OPERATING INSTRUCTIONS • 8DB10 • 864-5091.9