c) If the product is installed on a flammable floor, a floor protection must be installed. The floors made of flammable material,
such as moquette, parquet or cork etc., must be covered by a floor protector. SUCH FLOOR PROTECTOR SHALL BE A LISTED UL
1618 MATERIAL.
The floor protector shall be placed under the appliance and it must extend at least 16-in (419 mm) beyond the front and at least
8-in (203 mm) beyond each side of the fuel loading and ash removal opening (see
inches (mm)
ROSA XXL UL-C
ROSA L UL-C
MILLY UL-C
3.1.1 STRAIGHT INSTALLATION
Interior Vertical Vents
A2
3.1.2 FLOOR PROTECTION INSTALLATION REQuIREmENTS
Interior Vertical Vents
A2
B2
007098005-001
A1
A2
40 in (1016 mm)
10 in (254 mm)
40 in (1016 mm)
10 in (254 mm)
40 in (1016 mm)
10 in (254 mm)
A3
A2
A1
B3
A3
A2
B1
Floor Protection
A1
A3
15 in (381 mm)
15 in (381 mm)
15 in (381 mm)
B3
B2
Picture 1
A2
B2
B2
Picture 2
- distance b).
Picture 2
b1
b2
16 in (406 mm)
8 in (203 mm)
16 in (406 mm)
8 in (203 mm)
16 in (406 mm)
8 in (203 mm)
Through the wall installation
A3
A2
B2
B1
A1
Through the wall installation
B3
B1
Floor Protection
b3
2 in (50.8 mm)
2 in (50.8 mm)
2 in (50.8 mm)
A2
B2
B2
15