WAGO I/O SYSTEM 750 XTR
750-1416/040-000 8DI 24 VDC 0.2ms 2-wire XTR
Do not exceed maximum values via power contacts!
The maximum current that can flow through the power jumper contacts is 10 A.
The power jumper contacts can be damaged and the permissible operating
temperature can be exceeded by higher current values.
When configuring the system, do not exceed the permissible maximum current
value. If there is a higher power requirement, you must use an additional supply
module to provide the field voltage.
Pos : 32 /D okumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Pos : 33 /Serie 750 ( WAGO-I/O-SYST EM)/Ger ätebesc hrei bung (alte Str uktur)/Ansc hlüsse/Pus h-in C AGE C LAM P®-Ansc hlüsse - Übersc hrift 3 @ 15\mod_1370519905692_21.doc x @ 122018 @ 3 @ 1
3.2.3
Push-in CAGE CLAMP
Pos : 34 /Serie 750 ( WAGO-I/O-SYST EM)/Wic htige Erläuterungen (al te Str uktur)/Sic herheits- und sonstige Hinweis e/War nung/War nung: Speis ung aussc hließlic h aus SELV-/PELV-Versorgung (24V- XTR-I/O-Modul e) @ 29\mod_1493107132163_21.doc x @ 419618 @ @ 1
Power from SELV/PELV power supply only!
All field signals and field supplies connected to this XTR I/O module
(750-1416/040-000) must be powered from SELV/PELV power supply(s)!
Pos : 35 /Serie 750 ( WAGO-I/O-SYST EM)/Ger ätebesc hrei bung (alte Str uktur)/Ansc hlüsse/DI/Anschl üss e 750- 141x 8 D I 2-Leiter H SS Pus h-in C AGE C LAMP @ 7\mod_1274262794032_21.doc x @ 56626 @ @ 1
Figure 4: Push-in CAGE CLAMP
Table 5: Legend for Figure "Push-in CAGE CLAMP
Channel
1
2
7
8
Connectors
®
Connectors
®
Designation
Connector Function
DI 1
1
24 V
9
DI 2
2
24 V
10
DI 7
7
24 V
15
DI 8
8
24 V
16
Device Description
®
Connectors"
Input DI 1: Signal voltage
Input DI 1: Sensor supply +24 V
Input DI 2: Signal voltage
Input DI 2: Sensor supply +24 V
.
.
.
Input DI 7: Signal voltage
Input DI 7: Sensor supply +24 V
Input DI 8: Signal voltage
Input DI 8: Sensor supply +24 V