Setup Example (3) of 0 to 10 V Input and Unit

IM 04P02B01-02E
Setting the Input Range and Alarm on Measurement Channels
Selecting the Unit
16.
Use the
CHARACTER
key. (For the procedure, see "Entering Characters" on page 23. For the
characters that can be used, see "Explanation" on page 39.)
Unit:
CHR:%-
Finishing the Unit Setting
17.
When Setting complete screen is displayed, press the ESC key.
03-03 Channel
Setting complete
18.
Hold down the
Set channel 04 to 0 to 10 V input and measure the range 0.0 to 400.0 m
voltage range is used. The unit is converted using the linear scaling function. The scaling
range is –20000 to 30000 excluding the decimal point.
The measured values in the range of 0.0 to 400.0 m
mm on the chart paper.
–20 V
Chart paper
Entering Setting Mode
1.
Hold down the
Selecting the Range
2.
Press the
key with Range shown on the screen.
Set=Range
Input range and record
Selecting the Channel Range
3.
Press the
key to set the first channel to 04, and then press the
First channel Last channel
CH=04-04
First channel 01-06
4.
Likewise, set the last channel to 04 and then press the
* When the
key
the operation is reversed as when the respective key is pressed by itself.
key and
key to set unit character and then press the
key for 3 seconds to return to Operation mode.
MENU
Linear scaling Measurable range of 20 V
0.00 V
(Span left)
3
0.0 m
/h
(Scale left)
key for 3 seconds to enter Setting mode.
MENU
Displays a description of the setup item.
key or CHARACTER key is pressed while holding down the SHIFT key,
3
/h are recorded in a width of 180
10.00 V
400.0 m
180 mm
Displays the selectable range of channels.
key.
3
/h. The 20 V DC
20 V
(Span right)
3
/h
(Scale right)
key.
37