Water Drain Connections

Water Drain Specifications:
o
Evaporation chamber water drain temperature: 60°C.
o
Standard hydraulic fittings (supplied): a DN20 female compression fitting for the
evaporation chamber drain and a DN15 female elbow fitting for the pan drain.
2 hydraulic pipes (not supplied) must be placed underneath the humidifier and connected
to the drain pipes (see Illustration 29 - Water Supply and Drain Connections).
Use DN20 and DN15 standard copper hydraulic pipes.
Ensure that the drain pipe dimension is sufficient, especially if more than one humidifier is
evacuating into the same drain line.
The minimum drain pipe gradient must be of 6.5mm per 300mm.

Weather Proof Enclosure Plumbing Connection

Main Drain
¾" (DN20)
Illustration 30 - Weather Proof Enclosure Plumbing: Front View
www.neptronic.com
Installation Instructions and User Manual
Water Supply
½" NPT (DN15)
Pan Drain
Copper pipe (by others) field installed for
¾" (DN20)
connection to side outlets
SKE4-E Steam Humidifier
Page | - 29 -