Menu - Integration - Neptronic SKE4-E05 Installation Instructions And User Manual

Ske4-e series. steam humidifier
Table of Contents

Advertisement

Menu - Integration

[Level 5 - Requires level 5 password in order to access]
Sub-Menu
Setting
Device
DeviceName:
Location:
Description:
DeviceInstance:
HTTPServer
HttpServerUnits:
WebPriorityForWriting:
BACnetServer
Language:
ListMode:
Units:
BACnetMSTP
MaxMaster:
Network
MaxInfoFrames:
AutoBaud:
BaudRate:
MAC:
BACnetIP
BIPPort:
ModbusServer
Units:
ModbusRTU1In
MAC:
Autobaud:
PortConfig:
BaudRate:
www.neptronic.com
Default
[4]
-
-
-
0153001 (0x000255a9)
[2]
Metric
15
[3]
English
Integrator
Metric
[5]
127
1
Yes
38400
001
[1]
47808
[1]
Metric
[4]
1
No
No Parity, 2 Stop Bits
19200
Range
(* indicates no configuration; display only)
Metric, Imperial
min: 1, max: 16
(Language options vary based on region.)
Integrator, Advanced, Factory
Metric, Imperial
min: 1, max: 127
min: 1, max: 3
No, Yes
9600, 19200, 38400, 76800
min: 0, max: 65535
Metric, Imperial
min: 0, max: 247
No, Yes
No Parity, 2 Stop Bits
Even Parity, 1 Stop bit
Odd Parity, 1 Stop bit
9600, 14400, 19200, 38400, 57600
SKE4-E Steam Humidifier
Installation Instructions and User Manual
Description/Notes
Establish a name for the device.
Establish a designated location for the unit.
Establish a brief description for the unit.
Define the device instance value.
Select whether to use a metric or imperial system of units for the
HTTP server.
Set the priority level assigned for writing.
For models connected to the BACnet network.
Select the language for the BACnet server.
Select the category of BACnet objects to display.
Select whether to use a metric or imperial system of units for the
BACnet server.
For models connected to BACnet MSTP.
Configure MaxMaster value to increase network efficiency when there
are less than 127 devices on the network. For optimal efficiency, set
value to the highest MAC address in the MS/TP network.
Configure the maximum number of information messages the
controller may transmit, before it must pass the token to the next
controller.
Enable or disable automatic baud rate detection.
Select the baud rate for data transfer.
Set the MS/TP network MAC address.
For models connected to BACnet IP.
Set the User Datagram Protocol (UDP) port number.
BACnet port number is set by default.
For models connected to Modbus.
Select whether to use a metric or imperial system of units for the
Modbus server.
For models connected to Modbus.
Set the Modbus MAC address.
Enable or disable automatic baud rate detection.
Select the Modbus communication port configuration.
Select the baud rate for data transfer.