Menu - Installation

[Level 4 - Requires level 4 (or higher) password in order to access]
Sub-Menu
Setting
DrainInterval:
IdleTime:
BlowdownRate:
Quick Config
ServInterval:
ServOperation:
FillMode:
ControlProfile:
ModHLProfile:
RoomDemandLoop
RoomRHSrc:
RoomRHStptSrc:
Control
SupplyHLLoop
SupplyHLReadingSrc:
SupplyHLStpntSrc:
HumidityControl
HumCntrlDemandSrc:
HumCntrlHLSrc:
HumCntrlBinDemandSrc:
CntrlSigType:
RoomRHSigType:
Physical IO
SupplyRHSigType:
www.neptronic.com
Default
6hr
min: 0hr, max: 24hr
72hr
min: 24hr, max: 72hr
0%
min: 0%, max: 100%
1000hr
min: 1000hr, max: 3000hr
Allowed
Not Allowed, Allowed
Pulsed
OneShot, Pulsed
ExternAnalog, ExternNetwork, InternAnalog,
ExternAnalog
InternNetwork, InternTBD, Custom
Disabled, ExternAnalog, ExternNetwork,
Disabled
InternAnalog, InternNetwork, Custom
[2]
None
None, RoomRH, Network
None
None, Internal, ControlInput
[2]
None
None, SupplyHLRH, Network
None
None, Internal, ControlInput
[2]
ControlInput
None, ControlInput, RoomDemand, Network
None
None, ControlInput, SupplyHLDemand, Network
None
None, BinaryExtDemand
0-10Vdc
0-10Vdc, 2-10Vdc, 4-20mA, 0-20mA
0-10Vdc
0-10Vdc, 2-10Vdc, 4-20mA, 0-20mA
0-10Vdc
0-10Vdc, 2-10Vdc, 4-20mA, 0-20mA
Range
Set the frequency of the drain cycle. In general, a more frequent drain
cycle is required as the water hardness level rises. The drain cycle
setting does not affect the AFEC system.
Set the amount of time the humidifier can remain in standby mode until
an automatic drain cycle is performed.
Define the rate of boiler blowdown or water dilution, in order to minimize
water impurities.
Set the time of operation before the humidifier calls for servicing.
Select whether to enable the unit to continue producing steam, even
when it is due for servicing.
When set to Allowed, the unit will continue operating even when a
service alarm is active.
Select the water filling method for the fill valve:
When set to OneShot, water will continuously flow.
When set to Pulsed, water will flow in short bursts.
Select a preconfigured control mode profile for the modulating humidity
demand. Select the Custom option to configure individual settings.
(Network option only applicable for BACnet models.)
Select a preconfigured control mode profile for the modulating high limit
demand. Select the Custom option to configure individual settings.
(Network option only applicable for BACnet models.)
Only appears if ControlProfile is set to an internal control mode or
HumCntrlDemandSrc is set to RoomDemand.
Select the reading source for the room demand.
(Network option only applicable for BACnet models.)
Select the room demand setpoint source.
Only appears if ModHLProfile is set to an internal control mode or
HumCntrlHLSrc is set to SupplyHLDemand.
Select the reading source for the supply high limit demand.
(Network option only applicable for BACnet models.)
Select the supply high limit demand setpoint source.
Select the humidity control demand source for modulating humidifiers.
(Network option only applicable for BACnet models.)
Select the humidity control high limit source for modulating humidifiers.
(Network option only applicable for BACnet models.)
Select the humidity control demand source for On/Off humidifiers.
Select the signal type for the control demand analog input.
Select the signal type for the room humidity analog input.
(Only appears if ControlProfile is set to InternAnalog or
RoomRHSrc is set to RoomRH.)
Select the signal type for the duct or supply high limit humidity analog
input.
(Only appears if ModHLProfile is set to InternAnalog or
SupplyHLReadingSrc is set to SupplyHLRH.)
SKE4-E Steam Humidifier