Remote Installation - Humidifier With Sdu - Neptronic SKE4-E05 Installation Instructions And User Manual

Ske4-e series. steam humidifier
Table of Contents

Advertisement

Remote Installation - Humidifier with SDU

The SDU can be installed in a different location than the humidifier (remote SDU). Follow the piping
recommendations.
Mount the SDU to the wall on brackets (not supplied). Do not drill mounting holes through
the cabinet of the SDU.
Connect the steam hose to the bottom inlet of the SDU and to the humidifier steam outlet
located on top of the cabinet.
Secure the steam hose with the hose clamp (supplied).
Connect the condensate hose to the bottom of the SDU and to an open drain or to the
humidifier using the knockout hole located on the back of the cabinet.
Connect the electrical wires from the SDU to the top of the humidifier. Field wiring must
conform to local codes.
The fan of the SDU will operate for a period of five minutes after steam production has
stopped to prevent condensation.
Avoid any obstruction of the ventilation openings on top of the SDU.
Without
additional
18''
ventilation
(0.45 m)
54'' (1.35 m)
78''
(2 m)
www.neptronic.com
Installation Instructions and User Manual
Connect condensate
hose to humidifier
(back knockout hole)
Or to open drain
4''
(0.10 m)
Illustration 26 - SDU Remote Installation
SKE4-E Steam Humidifier
Field wiring
(by others)
Field piping
(by others)
Page | - 25 -

Advertisement

Table of Contents
loading

Table of Contents