S Trap Installation On The Steam Line - Neptronic SKE4-E05 Installation Instructions And User Manual

Ske4-e series. steam humidifier
Table of Contents

Advertisement

S Trap Installation on the Steam Line

The lowest point of any steam hose or rigid pipe must be the humidifier. If the humidifier
cannot be the lowest point of the piping, install one or more steam traps (S Type) at the
lowest point(s) of the steam supply piping. The steam separator (S trap) must be installed
higher than the static pressure of the system by at least 51mm.
Illustration 24 - Steam Output Connection: Incorrect Installation
Minimum 12''
(305mm)
www.neptronic.com
Minimum 12''
(305mm)
Use ''S'' separator when
the steam distributor is
lower than the humidifier
steam outlet
15%
Steam outlet
Connect to open drain
Illustration 25 - Steam Separator (S trap) Installation
SKE4-E Steam Humidifier
Installation Instructions and User Manual
15%
8''
(203mm)
Connect to open drain
15%
8"
Use "S" separator
(203mm)
when ceiling space is
limited and you need
to create 15% slopes
Page | - 23 -

Advertisement

Table of Contents
loading

Table of Contents