Start-Up - Neptronic SKE4-E05 Installation Instructions And User Manual

Ske4-e series. steam humidifier
Table of Contents

Advertisement

Start-Up

1. Proceed to start-up the humidifier, as follows:
a) Turn on the humidifier by pressing and holding the Power button
b) Verify that there is a humidity demand displayed on the LCD screen of
c) Ensure that the water supply valve connected to the humidifier is turned
Start-up
d) Verify the water level as water is filling the evaporation chamber by
e) Once the evaporation chamber has been filled, observe the system for
2. Check the location of the Airflow switch in the system and its operation by
Safety Test
stopping the fan. With no air movement, the humidifier should automatically
stop.
3. Turn off the humidifier by pressing and holding the Power
seconds.
4. Conduct a drain cycle by pressing and holding the Drain button
Drain and
seconds. Ensure that the evaporation chamber has been emptied.
Reset
5. Once the drain cycle is complete, restart the humidifier by pressing and
holding the Power
6. Reset the Airflow switch if needed.
End
7. The humidifier is now ready for normal operation.
www.neptronic.com
3 seconds. Verify that the controller Status Display LED is blue.
the humidifier.
on and that water is flowing directly to the humidifier water supply inlet.
Ensure that the water shut off valve is turned off.
using the control panel to access the WaterLevel setting located in the
Physical IO sub-menu of the General menu. Ensure that there are no
water leaks along the water line.
water and steam leaks during several minutes of operation.
button for 3 seconds.
SKE4-E Steam Humidifier
Installation Instructions and User Manual
for
button for 3
for 3
Page | - 51 -

Advertisement

Table of Contents
loading

Table of Contents