Menu - General [

Level 1 - No password required]
Press the menu button from the Idle Screen to access the General menu.
Sub-Menu
Setting
AirFlow:
SupplyHighLimit:
Interlock:
Status
OccupancyState:
SteamOutput:
BoilerDemand:
BoilerSteamOut:
ServiceDue:
Power:
State:
RoomDemand:
SupplyHLDemand:
Control
HumDemand:
ControlState:
AirFlow:
SupplyHighLimit:
Interlock:
BinExtDemand:
Physical IO
ControlInput:
RoomRH:
SupplyHLRH:
WtrLeakDet:
www.neptronic.com
Range
Default
(* indicates no configuration; display only)
Closed
* (Closed, Open)
Closed
* (Closed, Open)
Closed
* (Closed, Open)
Current value
* (Occupied, Unoccupied, Vacant, Off)
Current value
* (min: 0.00%, max: 100.00%)
Current value
* (min: 0.00%, max: 100.00%)
Current value
* (min: 0.00%, max: 100.00%)
Off
* (Off, On)
Current value
* (Off, On)
* (Off, Idle, LineRinse, TankRinse, Filling,
Current value
Draining, Heating, Boiling, Alarm)
Current value
* (min: 0.00%, max: 100.00%)
Current value
* (min: 0.00%, max: 100.00%)
Current value
* (min: 0.00%, max: 100.00%)
* (Normal, LowLimit, HighLimit, NoAirFlow,
Normal
Interlock)
Closed
* (Closed, Open)
Closed
* (Closed, Open)
Closed
* (Closed, Open)
0%
* (0%, 100%)
Current value
* (min: 0.00%, max: 100.00%)
Current value
* (min: 0.00%, max: 100.00%)
Current value
* (min: 0.00%, max: 100.00%)
Ok
* (Ok, Leak)
Installation Instructions and User Manual
Description/Notes
Displays the status of the airflow switch.
If Open is displayed, it indicates that the airflow is not detected by the air pressure switch.
Displays the status of the high limit contact.
If Open is displayed, it indicates that the humidity level has exceeded the setpoint on the high
limit humidistat.
Displays the status of the interlock.
If Open is displayed, it indicates that the humidifier is stopped as a result of the interlock safety
being open.
Displays the current occupancy state.
(Only appears if ControlProfile is set to an internal control mode or HumCntrlDemandSrc
is set to RoomDemand.)
Displays the measured steam output of the system.
Displays the measured humidity demand of the humidifier.
Displays the measured steam output of the humidifier.
Displays whether the humidifier is due for servicing.
Displays whether the humidifier is powered on or off.
Displays the current state of operation of the humidifier.
Displays the room humidity demand value.
(Only appears if ControlProfile is set to an internal control mode or HumCntrlDemandSrc
is set to RoomDemand.)
Displays the supply high limit humidity demand value.
(Only appears if ModHLProfile is set to an internal control mode or HumCntrlHLSrc is set
to SupplyHLDemand.)
Displays the current humidity demand value.
Displays the current state of the safety control circuit and whether the circuit has been
disconnected due to a safety switch.
Displays the status of the airflow switch.
If Open is displayed, it indicates that the airflow is not detected by the air pressure switch.
Displays the status of the high limit contact.
If Open is displayed, it indicates that the humidity level has exceeded the setpoint on the high
limit humidistat.
Displays the status of the interlock.
If Open is displayed, it indicates that the humidifier is stopped as a result of the interlock safety
being open.
Displays whether there is currently a humidity demand, when an On/Off humidifier is used.
(Only appears when using an On/Off humidifier.)
Displays the current control input reading.
Displays the room humidity reading value.
(Only appears if ControlProfile is set to InternAnalog or RoomRHSrc is set to RoomRH.)
Displays the supply high limit humidity reading value.
(Only appears if ModHLProfile is set to InternAnalog or SupplyHLReadingSrc is set to
SupplyHLRH.)
Displays whether a water leak has been detected.
If Leak is displayed, it indicates that there is a leak within the water line.
SKE4-E Steam Humidifier
Page | - 42 -