Positioning and Mounting - Weather Proof
Enclosure Unit

General Recommendations

Plan a location that is easy to access and permits an easy inspection and servicing of the
humidifier.
Do not install the humidifier where failure of the appliance could cause damage to the
building structure or to other expensive equipment.
Maintain the following minimum clearances while installing to enable access for
inspection and servicing.
Side
Top
Both sides
Front
The humidifier is designed to be installed directly on the floor/roof or a curb.
Provide a level, solid foundation for the humidifier.
Ensure that the floor/roof beneath the humidifier is water proof to withstand any water
spillage during servicing or if a problem occurs.
Attach the SKE4 enclosure securely and safely.
www.neptronic.com
20" (51cm)
12" (30cm)
minimum
42" (107cm)
minimum
Illustration 12 - Weather Proof Enclosure Unit
Minimum Clearance
51 cm
30 cm
107 cm
SKE4-E Steam Humidifier
Installation Instructions and User Manual
minimum
12" (30cm)
minimum
Page | - 16 -