14.
Trouble shouting guide
Problem
Indicator
Power: Off
Check: Off
Humidifier does
not operate
Fill: Off
(Power Off)
Steam: Off
Drain: Off
Power: On
Check: Off
Humidifier does
not operate
Fill: Off
(Power On)
Steam: Off
Drain: Off
Power: On
Check: Off
Humidifier does
not produce
Fill: Off
steam
(No Demand)
Steam: Off
Drain: Off
Humidifier does
Power: On
not produce
Check: Off
steam
Fill: Off
(Safety Open)
Steam: Off
Modulating
Drain: Off
humidifiers only
Power: On
No water inside
Check: On
the evaporation
chamber
Or
Fill: On
Humidifier will
not stop
Steam: Off
draining
Drain: Off
Power: On
Check: Off
Humidifier is
Fill: On
always on
Foam cycle
Steam: Off
Drain: On
Display
The humidifier is not
powered.
The low voltage fuse is
open.
The high temperature
switch is open.
Wires harnesses inside the
humidifier are not secured
properly.
The rocker switch is at the
OFF position.
N E P 2 . 5
Wire harness from the LED
S K E 2 0 M
display panel to the Main
pc board is not secured
properly.
Modulating humidifier: no
analog signal.
On/Off humidifier: no
demand from humidistat or
N O
air flow is not detected by
D E M A N D
air pressure switch or high
limit humidistat is open.
Control wires are not
properly secured to the
terminal blocks.
Air flow is not detected by
air pressure switch or high
S A F E T Y
limit humidistat is open.
O P E N
Control wires are not
properly secured to the
terminal blocks.
Humidifier is filling with
water and has not reached
N O
or is not reaching the high
L E V E L
of the water level sensor.
Humidifier is not filling with
water.
Excessive foaming
condition inside the
F O A M I N G
evaporation chamber.
C Y C L E
Foaming sensor is
grounded.
SKE Humidifier
Causes
Check for the main power
supply and fuses.
Check the transformer,
the low voltage fuse.
Check the high
temperature switch, the
wires harnesses and the
Main pc board.
Press the rocker switch to
the AUTO position.
Check the white color wire
harness.
Press the RESET button
on the Main pc board.
Verify the setting of the
humidistat.
Check the fan operation.
Check the operation of
the high limit humidistat.
Verify the connections of
the wires to the control
terminal blocks.
Check the fan operation.
Check the operation of
the high limit humidistat.
Verify the wires to the
control terminal blocks #1
& 2.
Verify if the drain valve is
manually open.
Check if the shut off valve
on the water supply line is
open.
Verify the operation of the
fill valve.
Check the fill valve
strainer and the external
strainer are not blocked.
Verify the quality of the
supply water.
Verify if chemical products
were used to clean the
evaporation chamber
during maintenance.
Rinse with water the
chamber properly.
Check the setting of the
Drain cycle. Reduce the
time between Drain
cycles.
User Manual
Corrective actions
33