Water Drain Connections

Water Drain Specifications:
Evaporation chamber water drain temperature: 60°C.
o
Standard hydraulic fittings (supplied): a DN20 female compression fitting for the
o
evaporation chamber drain and a DN15 female elbow fitting for the pan drain.
2 hydraulic pipes (not supplied) must be placed underneath the humidifier and connected
to the drain pipes (see Illustration 31 - Water Supply and Drain Connections).
Use DN20 and DN15 standard copper or stainless steel hydraulic pipes.
It is recommended that the installed drain piping is rated for 100°C.
Ensure that the drain pipe dimension is sufficient, especially if more than one humidifier is
evacuating into the same drain line.
The minimum drain pipe gradient must be of 6.5mm per 300mm.
The humidifier drain pipes do not require a drain trap and must be piped to an open drain.
The main drain pipe must have a minimum diameter of DN40.
Back
Ø
(DN20)
Minimum
8" (200mm)
www.neptronic.com
SKE4
Humidifier
Illustration 32 - Plumbing Connection to Open Drain
SKE4-E Steam Humidifier
Installation Instructions and User Manual
Front
Ø
(DN15)
Page | - 32 -