Positioning - Humidifier with SDU

The SDU must be installed in an environment where the air is relatively clean. This will
prevent the blower from getting clogged with dust.
The humidifier must be mounted such that the SDU fan section is at least 2 m above the
floor.
Allocate a minimum clearance of 0.45 m from the ceiling to avoid ceiling and wall
condensation.
If additional ventilation is not present, ensure that the fan has a clearance of at least 1.35
m from the ceiling. Proper ventilation must be observed to avoid ceiling and wall
condensation.

Maintenance of the SDU

Clean the blower if there is an accumulation of dust.