Appendix B: Electrical Specifications; B.1: Electrical Specifications - Notifier NFS2-640/E Installation Manual

Fire alarm control panel
Hide thumbs Also See for NFS2-640/E:
Table of Contents

Advertisement

Appendix B: Electrical Specifications

B.1 Electrical Specifications
AC Power
Component
Main Power Supply
Wire size
NOTE: If using an auxiliary power supply such as FCPS-24S6/S8, APS-6R, ACPS-2406, or
ACPS-610, or audio amplifiers, refer to the documentation for that equipment.
Batteries
The control panel uses only sealed lead-acid batteries for secondary standby power. Maximum
battery capacity for the CPS-24/E main power supply is 200 AH. CAB-4 Series backboxes provide
space for two 26 AH (or smaller) batteries. Use external battery boxes if the installation requires
larger capacity batteries; see Table A.5, "Selecting Battery and Battery Backbox," on page 69.
The table below contains battery charger specifications.
Charger
CPS-24/E
Main Power Supply
CHG-120
Battery Charger
ACPS-2406
Auxiliary
Charger/Power
Supply
ACPS-610
Addressable
Charger/Power
Supply
Signaling Line Circuit (SLC)
Item
Voltage
Maximum length
Maximum current
Maximum resistance
70
Values
120 VAC, 50/60 Hz, 5.0 A; or
240 VAC, 50/60 Hz, 2.5 A
Maximum 12 AWG (3.31 mm
Description
An internal battery charger
for 18 AH to 200 AH
An external battery charger
designed to charge lead-acid
batteries between 26 AH and
120 AH
An internal battery charger
for 7AH to 26 AH
An internal battery charger
for 12AH to 200AH
Value
24 VDC nominal, 27.6 VDC maximum
12,500 ft. (3810 m) total loop or circuit length (NFPA Style 4, 6 and 7)
Note: Refer to Appendix B.2 "Wire Requirements" for limitations.
400 mA peak, 200 mA average (max short circuit; circuit will shut down until
short is fixed). For battery calculation purposes use 200mA.
50 ohms (supervised and power-limited)
NFS2-640/E Installation Manual — P/N 52741:P2 7/10/14
2
) with 600 VAC insulation
Specifications
Normal Charge: 27.6 VDC +/- 0.24 VDC
Charging Current: 2.0 A or 5.7 A (Software selectable)
Dual Rate: High Charge: 28.1 VDC
Normal Charge: 27.6 VDC
Charging Current: 4.5 A
Normal Charge: 27.6 VDC
Charging Current: 1.1 A max (0.750 A typical)
Normal Charge: 27.6 VDC +/- 0.24 VDC
Charging Current: 2A, 5A, or OFF (Software Selectable)

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents