5: Connecting Multiple Printers, Crts, Or Crt/Prn Combination; Wiring A Signaling Line Circuit (Slc) - Notifier NFS2-640/E Installation Manual

Fire alarm control panel
Hide thumbs Also See for NFS2-640/E:
Table of Contents

Advertisement

Installation
3.13.5 Connecting Multiple Printers, CRTs, or CRT/PRN
Combination
Connecting multiple devices requires changing the CRT-2 setup using the F1(Quick) menu:
Set Host/Printer=EIA/AUX.
Set EIA Data Format=8/1/N.
If the AUX device is a printer, set the Printer and AUX Data Format=7/1/E.
If the AUX device is a second CRT-2, set the AUX Data Format=8/1/N.
Connect multiple devices as shown in Figure 3.28.
Note: For wire requirements, see Table B.1 in Appendix B.1 "Electrical Specifications".
Figure 3.28 Connecting Multiple Devices on the EIA-232 Circuit

3.14 Wiring a Signaling Line Circuit (SLC)

Overview
Communication between the control panel and intelligent and addressable initiating, monitor, and
control devices takes place through a Signaling Line Circuit (SLC). You can wire an SLC to meet
the requirements of NFPA Style 4, Style 6, or Style 7 circuits. This manual provides requirements
and performance details specific to this control panel; for installation information and general
information, refer to the SLC Wiring Manual.
Wiring
Maximum wiring distance of an SLC using 12 AWG (3.31 mm
total twisted-pair for Style 4, Style 6 and Style 7 circuits.
Capacity
The NFS2-640/E provides one (1) SLC, with a total capacity of 318 intelligent/addressable devices:
01-159 intelligent detectors
01-159 monitor and control modules
An optional expander board provides one (1) additional SLC, with the same capacity.
Units employing multiple detector operation shall include a minimum of two detectors in each
protected space and reduce the detector installation spacing to 0.7 times the linear spacing in
accordance with National Fire Alarm Code, NFPA. For spacing requirements refer to the detector's
installation instruction.
46
To AUX Port of CRT-2
To EIA-232 port of CRT-2
(female socket shown)
(female socket shown)
To EIA-232 port of next
CRT-2 or PRN (female socket shown)
NFS2-640/E Installation Manual — P/N 52741:P2 7/10/14
Wiring a Signaling Line Circuit (SLC)
To Control Panel
TB12-PC/CRT REF
TB12-PC/CRT TX
TB12- PC/CRT RX
2
) wire is 12,500 feet (3810 meters)