7.9.

Inputs configuration

For every input the following settings shall be determined respectively.
7.9.1.1.
This parameter allows us to determine the steady state of the input. Change of this
state results in sending information on alarm. Allowable NC and NO input. NC input
shall be shorted to ground. Actuation follows after decay. NO input remains open.
At this moment of shortening to ground activation follows. EOL and DEOL are
options where you use 1 or 2 resistors to distinguish alarm from sabotage
7.9.1.2.
This parameter means minimum time for change maintenance at input so that it
would be detected by transmitter. Factory setting is 400ms.
7.9.1.3.
With this option you can lock any input of module, and as a result condition changes
on this input will be ignored and will not be reported to monitoring station. Lock
may be persistent or temporary.
In case of temporary lock – user can set lock time and number of input state
changes after which lock occurs. Lock time is counted from first input state change.
Both types of lock can be deactivated by SMS command (see RLIMIT command
described in chapter 9).
LX2N_Manual_en-1.11i66
NO/NC/EOL-NO/EOL-NC/DEOL-NO/DEOL-NC
Configuration of LX2N inputs

Delay [ms]

Lock

Page 27 / 56