Installation Space Ras-(8-18)Fsxn - Hitachi FSXN Series Service Manual

Table of Contents

Advertisement

2 Unit installation

2.1.3 Installation space RAS-(8-18)FSXN

> 500 + h2/2
N O T E
Side view. All measurements are in mm.
Calculate the service space required during the installation of the unit, based on the following:
If there are no walls in front of or behind the unit, a space of 500 mm is necessary in front -A- and 300 mm behind -B-.
If the front wall is higher than 1500 mm, a space of (500 + h2/2) mm is required at the front -A-.
If the rear wall is higher than 500 mm, a space of (300 + h1/2) mm is required at the back -B-.
If a wall -D- is installed in front of the unit, a ventilation hole -C- should be made in the wall.
When the space over the unit is less than 1500 mm, or the space around the unit is closed, a duct is required to prevent
short-circuits between the inlet air and the discharge air.
If there are any obstacles in the space over the unit, the four sides of the unit should be left open.
10
SMGB0065 rev. 1 - 12/2010
D
C
A
765
B
> 300 + h1/2

Advertisement

Table of Contents
loading

Table of Contents