6 Optional functions
Function setting
No.
Setting item
Indoor unit fan control during the
1
Thermo-OFF in heating mode
2
Night-shift
Cancellation of the outdoor ambient
3
temperature limit.
Defrost for cold area (change in the
4
defrost condition)
5
SLo (fan speed) Defrost setting
6
Cancellation of the hot start
7
Priority capacity mode
Target value of the compressor
8
frequency for cooling
Target value of the compressor
9
frequency for heating
128
SMGB0065 rev. 1 - 12/2010
7-segment display
SEG2
SEG1
00
No setting
FA
Forced connection and disconnection on the indoor unit fan (2 minutes ON / 6
01
minutes OFF).
00
No setting
ni
01
Setting of night-shift
00
No setting
01
For heating
GS
02
For cooling
03
For cooling/heating
00
No setting
Jo
01
Defrost operation condition 2
Stopping the Indoor unit fan when the heating operation is turned on during the
00
defrost operation
01
Indoor unit SLo fan operation during the defrost operation
bJ
02
Indoor unit SLo fan operation when the heating operation is activated
Fan operation when the heating operation is activated/Operation of the indoor
03
unit SLo fan during defrost operation
00
Hot start available
HT
01
Cancellation of the hot start
00
No setting
01
Change in the maximum frequency limit value
nU
02
Change in the current limit value
03
Change in the maximum frequency limit value and the current limit value
00
Initial setting (Targeted value of the Ps evaporating temperature 7 °C)
01
Targeted value (2 °C)
02
Targeted value (3 °C)
03
Targeted value (4 °C)
Hc
04
Targeted value (5 °C)
05
Targeted value (9 °C)
06
Targeted value (10 °C)
07
Targeted value (11 °C)
08-09
Not prepared (If set, the setting item will be ignored by the control PCB)
00
Initial setting (Targeted value of the Ps 2.85 MPa)
01
Targeted value (2.60 MPa)
02
Targeted value (2.75 MPa)
03
Targeted value (2.80 MPa)
Hh
04
Targeted value (2.82 MPa)
05
Targeted value (2.88 MPa)
06
Targeted value (2.90 MPa)
07
Targeted value (2.95 MPa)
08-09
Not prepared (If set, the setting item will be ignored by the control PCB)