5.1.2 Compressor operation control

¿
Compressor rotation control
The compressor rotation control is carried out to match its operation time in each of the outdoor units.
This control is carried out during the Thermo-OFF of the outdoor unit.
In case of switch-OFF or Thermo-OFF after 120 minutes of operation, the inverter compressor with the shortest operation
time will be preferably turned on.
N O T E
In order to carry out this function, at least two outdoor units are required.
The operating sequence of the compressor rotation is described below.
RAS-20FSXN
Outdoor unit 1
Last time
Currently
Next time
-I-
Inverter compressor
RAS-(22-26)FSXN
Outdoor unit 1
-I-
Last time
1
Currently
2
Next time
1
-I-
Inverter compressor
-C-
Constant compressor
89
SMGB0065 rev. 1 - 12/2010
Cooling
Contents
Compressor
operating: ON
Compressor
stopped: OFF
Outdoor unit 2
-I-
1
2
2
1
1
2
Outdoor unit 2
-C-
-I-
3
2
3
1
3
2
Heating
Heat recovery
Purpose
Contents
Shut-off of high
Compressor
and low pressure
operating: ON
in the cycle during
Compressor
stoppage
stopped: OFF
Defrost
Contents
Open
5

Advertisement

Table of Contents
loading

Table of Contents