8 Troubleshooting
Code
Category
21
High pressure sensor
22
Outdoor air thermistor
23
Discharge gas thermistor at top of compressor
Outdoor unit
sensor
24
Heat exchanger liquid pipe thermistor
25
Heat exchanger gas pipe thermistor
29
Low pressure sensor
31
Incorrect capacity setting on outdoor and indoor units
35
System
Indoor unit no. incorrectly set
Abnormality in the collection circuit for outdoor unit
38
protection
Abnormal operation current in constant speed
39
Compressor
compressor
3A
Abnormal outdoor unit capacity.
Voltage or combination of outdoor unit models
3b
Outdoor unit
incorrectly set
Abnormal transmission between the main unit and the
3d
secondary unit(s)
43
Low-pressure decrease protection device activation
44
Low-pressure increase protection device activation
Protection device
45
High pressure increase protection device activation
Low-pressure decrease protection device activation
47
(vacuum protection)
48
Inverter overcurrent protection device activation
51
Sensor
Abnormal inverter current sensor
53
Inverter error signal detection
Inverter
54
Abnormal inverter fin temperature
55
Inverter fault
57
Fan controller protection activation
5A
Abnormal fan controller fin temperature
Fan controller
5b
Overcurrent protection activation
5C
Abnormal fan controller sensor
Compressor protection alarm (cannot be reset from the
EE
Compressor
remote controller)
Outdoor unit
Unit number or address number of the outdoor unit
b1
number setting
incorrectly set
Indoor unit
b5
Connection number of the indoor unit incorrectly set
number setting
C1
Incorrect indoor unit connection
C2
CH unit
Connection number of the indoor unit incorrectly set
C3
Incorrect indoor unit connection
169
SMGB0065 rev. 1 - 12/2010
Content of abnormality
Possible cause
Incorrect wiring, disconnected wiring, broken cable, short
circuit.
Combination capacity incorrectly set. Excessive or insufficient
total indoor unit capacity.
Indoor unit no. duplicated in same reference group.
Protection detection device fault (incorrect wiring of outdoor
PCB).
Overcurrent, blown fuse, current sensor fault, instant power
failure, voltage drop, abnormal power supply.
Outdoor unit capacity >54 HP.
Voltage or combination of secondary and main units incorrectly
set.
Incorrect wiring, disconnected wiring, broken cable, PCB fault.
Defective compression (compressor or inverter fault, loose
power supply connection).
Overload during cooling, high temperature with heating, locked
expansion valve (loose connector).
Overload (clogging, short pitch), pipe clogging, excess
refrigerant, mixture of inert gas.
Insufficient refrigerant, refrigerant pipes, clogging, expansion
valve locked in open position (loose connector).
Overload, compressor fault.
Current sensor fault.
Controller IC error signal detection (overcurrent, low-voltage
and short-circuit protection).
Abnormal inverter fin thermistor, heat exchanger clogging, fan
motor fault.
Inverter PCB fault.
Controller IC error signal detection (overcurrent, low-voltage
and short-circuit protection), instant overcurrent.
Fin thermistor fault, heat exchanger clogging, fan motor fault.
Fan motor fault.
Current sensor fault (instant overcurrent, increased fin
temperature, low voltage, earthing fault, step-out).
This alarm code is displayed when the following alarms are
triggered three times within six hours: 02, 07, 08, 39, 43 to 45,
47.
A number greater than 64 has been set for the refrigerant cycle
or address.
There are more than 17 units not corresponding to H-LINK II
connected to one system.
There are 2 or more CH units connected between the outdoor
and indoor units.
There are 9 or more indoor units connected to the CH unit
Indoor units from different refrigerant cycles have been
connected to the CH unit.