8 Troubleshooting
Press PSW4 (▼) to move forward or PSW2 (▲) to move back.
Select the indoor unit number for indication.
Press PSW3 (►) for more detailed information on the unit number selected.
Unit no.
Indication
No. 0
No. 1
No. 63
Press PSW4 (▼) to move forward or PSW2 (▲) go back.
This information will be alternatively indicated as "Item" → "Details".
Press PSW5 (◄) to return to the indoor unit No. selection.
Indication details:
Item
1
Capacity of the indoor unit
2
Opening of the expansion valve
Heat exchanger liquid pipe
3
temperature
Heat exchanger gas pipe
4
temperature
5
Air inlet temperature
6
Air outlet temperature
7
Unit stoppage cause code
NOTE: The indoor unit No. is indicated on "SEG1"
Capacity table for the indoor units.
Capacity
Horsepower
Indication
(kW)
6
2.2
8
2.8
10
3.8
11
4.0
13
5.2
(E) Cause for alarm code information
This information is indicated in unit A (main unit) only.
Press PSW4 (▼) to move forward or PSW2 (▲) to go back.
This information will be indicated alternating as "Item" → "Details".
253
SMGB0065 rev. 1 - 12/2010
d00
d01
d63
7-segment display
SEG2
CA
E
L
G

o
d1
(Example)
SEG2 SEG1
Capacity
Indication
(HP)
0.8
14
1.0
16
1.3
18
1.5
22
1.8
32
SEG1
Unit capacity indication.
00
Refer to the "Capacity table for the indoor units".
Unit: %
00
Unit: °C
00
Unit: °C
00
Unit: °C
00
Unit: °C
00
Indoor unit stoppage cause code indication.
00
Refer to the "Indoor unit stoppage cause table".
Horsepower
Indication
kW)
(HP)
5.6
2.0
40
6.7
2.3
48
7.1
2.5
64
8.0
3.0
80
11.2
4.0
Details
Capacity
Horsepower
(kW)
(HP)
14.0
5.0
16.0
6.0
22.4
8.0
28.0
10.0
8