12 Maintenance notes
Model
RAS-26FSXN
RAS-28FSXN
RAS-30FSXN
4
Special attention should be given to areas where the refrigerant may be deposited and stay in the room, such as
basements or similar, as it is heavier than air.
Example:
A: Refrigerant charge: 60 kg.
B: Refrigerant piping.
C: Outdoor unit.
D: Indoor unit.
E: Mechanical ventilation equipment.
F: Gas leak detector.
G: The smallest opening room.
H: Small room.
I: Medium-sized room.
J: Large room.
K: Opening.
N O T E
1
The gas leakage quantity for each room (large, medium-sized, small and the smallest) should be calculated as
60 kg.
2
The gas concentration of each room should not exceed the limit value, 0.44 kg/m
353
SMGB0065 rev. 1 - 12/2010