Hitachi FSXN Series Service Manual page 135

Table of Contents

Advertisement

6 Optional functions
No.
Setting item
Target value of the Indoor unit
10
expansion valve control for cooling
Target value of the Indoor unit
11
expansion valve control for heating
Indoor expansion valve opening
12
change for stoppage indoor unit in
heating mode
Indoor expansion valve opening
13
change for Thermo-OFF indoor unit
in heating mode
Indoor expansion valve initial
14
opening of Thermo-ON indoor unit
in heating mode
Fine adjustment of indoor
15
expansion valve initial opening in
cooling mode
Fine adjustment of indoor
16
expansion valve initial opening in
heating mode
129
SMGB0065 rev. 1 - 12/2010
7-segment display
SEG2
SEG1
00
Initial setting (Targeted value of the SH +5 °C)
01
SH targeted value 7
02
SH targeted value 6
SC
03
SH targeted value 4
04
SH targeted value 3
05-09
Not prepared (If set, the setting item will be ignored by the control PCB)
00
Initial setting (Target value of the SC +5 °C)
01
SC targeted value 11
02
SC targeted value 8
SH
03
SC targeted value 2
04
SC targeted value -1
05-09
Not prepared (If set, the setting item will be ignored by the control PCB)
00
Initial setting (stoppage unit expansion valve opening) (150 - 325 pulses)
Opening of the expansion valve (0.8-2.6) HP: 175 pulses, 2.5 HP or greater: 300
01
pulses
Si
Opening of the expansion valve (0.8-2.6) HP: 100 pulses, 2.5 HP or greater: 150
02
pulses
03-09
Not prepared (If set, the setting item will be ignored by the control PCB)
00
Thermo-OFF unit expansion valve opening (150 - 325 pulses)
Opening of the expansion valve (0.8-2.6) HP: 175 pulses, 2.5 HP or greater: 300
01
pulses
So
Opening of the expansion valve (0.8-2.6) HP: 100 pulses, 2.5 HP or greater: 150
02
pulses
03-09
Not prepared (If set, the setting item will be ignored by the control PCB)
00
Initial setting (300 - 650 PK)
01
2000 pulses
02
1400 pulses
ci
03
1000 pulses
04
600 pulses
05-09
Not prepared (If set, the setting item will be ignored by the control PCB)
00
Initial setting
01
Initial opening in cooling operation -2%
02
Initial opening in cooling operation +1%
cb
03
Initial opening in cooling operation +3%
04
Initial opening in cooling operation +5%
05-09
Not prepared (If set, the setting item will be ignored by the control PCB)
00
Initial setting
01
Initial opening in heating operation -2%
02
Initial opening in heating operation +1%
ch
03
Initial opening in heating operation +3%
04
Initial opening in heating operation +5%
05-09
Not prepared (If set, the setting item will be ignored by the control PCB)
Contents
6