8 Troubleshooting
C2
Alarm code
The unit no., alarm code ("35") and the unit code are alternately indicated in the temperature setting section of the indoor
unit connected to the CH unit.
LED (LED4, 5, 6) in PCB(1) of the CH unit flashes.
* < Heat recovery system (3 pipes) >
This alarm is indicated when nine or more indoor units are connected to the CH unit.
Are 9 or more indoor units
connected to CH unit?
No
Alarm code "C2" will be indicated when the units are connected as follows.
Outdoor Unit
(Ref. Cycle Group: 1)
CH Unit
Indoor Unit 1
Indoor Unit 2
(Ref. Cycle Group: 1)
(Ref. Cycle Group: 1)
236
SMGB0065 rev. 1 - 12/2010
Incorrect setting of the indoor unit connection number (CH unit).
PCB1: Control PCB in Outdoor Unit
PCB(1): CH Unit PCB
Yes
Indoor Unit 3
(Ref. Cycle Group: 1)
Correctly connect the wiring
and reset the power supply.
Failure of PCB(1) in CH unit
Indoor Unit 9
(Ref. Cycle Group: 1) 1)