10.6 Corrective maintenance
The following section describes how to de-energize the drive using the
local operator panel of the drive.
10.6.1 Overview on maintenance tasks
Visual checks on the drive
Cleaning
Checking wire and cable connections
Replacing filter mats
Replacing a phase module
Replacing a fan
10.6.2 Safety
!
Hazardous voltages!
Before starting to work on the drive, make sure
that:
• the main and auxiliary power supply to the drive
is switched off, locked out, and tagged out,
• the drive is dead,
• safety ground connections are in place,
• personal protective equipment is provided and
used when required,
• everyone involved is informed.
Before energizing the drive again, make sure that:
• all foreign objects are removed from the drive,
• all internal and external covers are securely fas-
tened and all doors are closed, locked and / or
bolted,
• the manual release of the door safety switch is
in the locked position.
!
Hazardous voltages!
When a phase module is removed from the cabinet,
the grounding path between grounding switch and
PE ground busbar is interrupted.
For this reason, connect grounding equipment at
the appropriate locations. The grounding equip-
ment ensures that hazardous voltages cannot be
fed into the drive from the main power supply or
the motor.
DANGER
DANGER
NOTICE
Foreign matter and particularly metallic dust can
cause failure and damage when the drive is ener-
gized.
Ensure that foreign matter cannot enter the cabi-
net:
• Close the doors and cover openings completely
when work is discontinued.
• Retrieve any foreign matter which accidentally
dropped into the cabinet.
10.6.3 De-energizing the drive locally
If the drive is controlled from remote, follow the
established shutdown procedures.
Stopping the motor
1. Enable the local control mode of the CDP con-
trol panel.
For further information, see
remote
control.
2. Stop the motor.
For further information, see
drive.
When the motor has reached zero speed, the
display shows ReadyRun.
1 L ->
StateINU
MOTOR SP
POWER
De-energizing the drive
3. To disconnect the drive from the main power
supply, press the SUPPLY OFF pushbutton. The
following takes place:
-
The MCB opens.
9.8 Local and
8.7 Stopping the
600.0 rpm 0
ReadyRun
0.00 rpm
0.0 kW