4.1 Safety
The drive must only be handled by personnel who are skilled and
experienced in unpacking and transporting heavy equipment.
4.2 Transport conditions
Transformer, Converter and Fans are considered separate
transport sections.
The transport conditions for the drive are based on
IEC 60721-3-2 'Classification of environmental con-
ditions: Classification of groups of environmental
parameters and their severities; Transportation'.
Table 4-1 Table 4.1 Transport Conditions
2K12 Climatic conditions
2B1 Biological conditions
2M4 Mechanical conditions
Low air temperature
High air temperature
• Unventilated enclosures
• Ventilated enclosures / outdoor
Relative humidity
Absolute humidity
Flora
Fauna
Stationary vibration random
• Acceleration spectral density
Non-stationary vibration (including shock)
• Shock response spectrum
Free fall
Toppling
Rolling, pitching
• Angle
• Period
Steady-state acceleration
-45 °C
70 °C
40 °C
100%
60%
No
No
2
3
10 m
/s
(2 – 3 Hz)
1 m2/s3 (10 - 20 Hz)
2
3
0.5 m
/s
(50 – 2000 Hz)
2
100 m/s
, 11 ms duration
2
300 m/s
, 6 ms duration
0.1 m
No
No
No
2
20 m/s