CHAPTER 6 – ELECTRICAL INSTALLATION
6.4 Parallel routing of power cables
While connecting the drive to the non-integrated transformer and the
motor, the following rules must be observed:
Independent of the distance between the non-inte-
grated transformer and the drive, one single-core
cable per phase must be used. The current carrying
capacity must not be increased by laying cables in
parallel.
Cables between drive and motor can be laid in par-
allel. The number of cables laid in parallel is limited
by the number of entry holes of the entry plate.