8.1 Operating conditions
The operating conditions for the drive are according to IEC 60721-3-3 '
Stationary use at weather-protected locations' (unless indicated
otherwise).
Table 8-1 Operating conditions
3K3 Climatic conditions
3B1 Biological conditions
3C2 Chemically active substances
3S2 Mechanically active substances
3M3 Mechanical conditions
If the operating conditions are not within the spec-
ifications, contact ABB.
Air temperature
Relative humidity
Absolute humidity
Condensation
Flora
Fauna
Sea salt and road salts
Sulphur dioxide
Hydrogen sulfide
Chlorine
Hydrogen chloride
Hydrogen fluoride
Ammonia
Ozone
Nitrogen oxides
Sand
Dust (suspension)
Dust (sedimentation)
Stationary vibration sinusoidal
Displacement amplitude
Acceleration amplitude
Non-stationary vibration (including shock)
Shock response spectrum
For the maximum ambient temperature,
see the
rating label
of the drive.
5 – 40 °C
5 – 85%
3
1 – 25 g/m
No
No
No
Salt mist
Mean value
3
0.3 mg/m
3
0.1 mg/m
3
0.1 mg/m
3
0.1 mg/m
3
0.01 mg/m
3
1 mg/m
3
0.05 mg/m
3
0.5 mg/m
3
30 mg/m
3
0.2 mg/m
3
1.5 mg/m
1.5 mm (2 – 9 Hz)
2
5 m/s
(9 – 200 Hz)
2
70 m/s
Max. value
3
1.0 mg/m
3
0.5 mg/m
3
0.3 mg/m
3
0.5 mg/m
3
0.03 mg/m
3
3 mg/m
3
0.1 mg/m
3
1.0 mg/m