ACS2000 DFE UM 3BHS360367 ZAB E01 REV. K
Analog inputs
Table 3-12 Optional analog input signal allocation
Terminal
X31-1
X32-1
X31-2
X32-2
X31-3
X32-3
X31-4
X32-4
X31-5
X32-5
Analog outputs
Table 3-13 Optional analog output signal allocation
Terminal
X31-6
X32-6
X31-7
X32-7
3.3.5 Fieldbus communication interfaces (option)
Overview
Fieldbus communication interfaces are used for
the bidirectional communication between the drive
and a higher-level process control system. Typi-
cally, operational commands, status messages of
the drive, speed or torque reference values, and
actual values are transmitted.
AF 100
Terminal allocation
X1A:1
X1B:1
X1B:2
X1B:3
X2:1
X2:2
X2:3
X2:4
Channel
Default setting
+10 V
Internal supply voltage
0 V
AI1+
Motor winding U1 temperature
AI1-
AI2+
Motor winding V1 temperature
AI2-
AI3+
Motor winding W1 temperature
AI3-
AI4+
Freely programmable
AI4-
Channel
Default setting
AO1+
Freely programmable
AO1-
AO2+
Freely programmable
AO2-
For further information on data transmis-
sion and on data and signal allocation to
the transmitted datasets, see:
Signal and parameter table
Installation and start-up guide of the
installed fieldbus interface
Engineering documents
L-
0 V supply in
L+
24 V (DC) supply in
L+
24 V (DC) supply out
SA
Redundant power supply "A" monitoring input
+
+ Signal
-
- Signal
SH
Shield
SH
Shield
Available fieldbuses
The drive can be equipped with one of the follow-
ing fieldbus interfaces.
Fieldbus
AF 100 fieldbus communication interface
Modbus TCP
Modbus RTU
Profibus DP
Customer connections
Par. group
Par. group
Interface type
CI810
NETA-21
NMBA-01
NPBA-12