64
ACS2000 DFE UM 3BHS360367 ZAB E01 REV. K
4.5 Storage
The drive can be stored for up to one year in the original packaging as
long as they are not damaged or opened. For information on longer
storage periods, contact the ABB service organization.
4.5.1 Storage conditions
The minimum requirements for storage are based
IEC 60721-3-1 'Classification of environmental
on
conditions: Classification of groups of environ-
mental parameters and their severities; Storage'
Table 4-2
1K22 Climatic conditions
1Z3 Special climatic conditions
1B1 Biological conditions
1M12 Mechanical conditions
4.5.2 Storage
If the drive is taken out of service for a longer time
proceed as follows:
1. Cover all cable inlets and ventilation slots with
an impermeable plastic or aluminum foil and
a wooden panel.
2. Add a desiccant of the appropriate quality:
-
The following quantity is needed when using
a polyethylene foil:
-
3. Close and lock the doors of the cabinet.
4. Use polyethylene or equivalent for packaging:
-
5. Attach humidity indicators to the packaging.
Check the storage conditions and the packaging
regularly. Repair any damages that occur during
the storage period immediately.
Storage conditions
.
Air temperature
Relative humidity
Absolute humidity
Movement of surrounding air
Flora
Fauna
Vibration
Acceleration spectral density
1 unit desiccant (30g) absorbs 6 g water
vapor.
2
10 units/m
foil
2
0,3g/m
/24h water vapor diffusion
-25 – +55 °C (drive)
-5 – +55 °C (spare parts)
10 – 100%
0.5 – 29%
30 m/s
Negligible
Negligible
2
0.1 m/s
(5 – 200 Hz)