10-3-2 Error Codes

Error
Contents
code
code
0101
Transmission failed; local node
Hex
not in Network
0103
Transmission failed; retry count
Hex
exceeded
0104
Transmission failed; maximum
Hex
number of frames exceeded.
0105
Transmission failed; node
Hex
address incorrect
0106
Transmission failed; redundant
Hex
node address
0107
Transmission failed; destination
Hex
node not in Network
0109
Transmission failed; destination
Hex
busy
010A
Transmission failed;
Hex
communications controller error
010D
Transmission failed; destination
Hex
address incorrect
010E
Transmission failed; routing
Hex
tables not registered
010F
Transmission failed; routing
Hex
table error
0110
Transmission failed; too many
Hex
relay points
0111
Transmission failed; command
Hex
packet too long
0112
Transmission failed; header
Hex
error.
0117
Internal buffer full
Hex
0118
Illegal packet discarded
Hex
174
The following table lists the error codes (in 4-digit hexadecimal) and the contents
of the errors.
Detail code
1st byte
2nd byte
Command block
Bits 0 to 7:
Source node address
Bits 8 to 14:
Bits 8 to 14:
Source Network
address
Bit 15:
OFF
Response block
Response block
Bits 0 to 7:
Destination node
address
Bits 8 to 14:
Bits 8 to 14:
Destination Network
address
Bit 15:
ON
(1st byte: bits 8 to 15;
2nd byte, bits 0 to 7)
Correction
Refer to 10-1 Troubleshooting
Using Indicators and place the
local node into Network.
Using the Controller Link Support
Software or FINS commands, run
echoback test and check
operating environment if errors
occur.
Reduce the number of events per
communications cycle or increase
the maximum number of network
parameter frames.
Refer to Section 3 Software
Installation and check node
address settings to be sure they
are within range and unique.
Correct node addresses so that
they are unique within the same
Network.
Refer to 10-1 Troubleshooting
Using Indicators and place
destination node into Network.
Increase number of retries or
reconfigure system to distribute
load.
Conduct an echoback test and if
the effects of noise are
considerable, reconsider the
operating environment. Restart
the Controller Link Support Board.
If the error occurs again, replace
the Board.
Check routing tables.
Check routing tables and system
configuration. Do not try to access
Networks separated by more than
one other Network.
Be sure to use the correct FINS
command format.
Increase number of retries or
reconfigure system to distribute
load.
Check for nodes sending illegal
packets.
Section
10-3
Recorded
in
in
EEPROM
No
No
No
No
No
No
No
Yes
No
No
No
No
No
No
No
Yes