NEC Power-Limited Wiring Requirements for eFlowNA8D Models:
Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit
wiring must remain at least 0.25" away from any non power-limited circuit wiring. Furthermore, all power-limited
circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits.
One such example of this is shown below. Your specific application may require different conduit knockouts to
be used. Any conduit knockouts may be used. For power- limited applications use of conduit is optional. All field
wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute).
Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods.
For Canadian installations use shielded wiring for all connections.
Note: Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire (Fig. 4a).
Fig. 4
Input
120VAC
60Hz
(non power-
limited)
ACM8CB
outputs
(power-
limited)
Fig. 4a
Incorrect Wire
Handling
Insulation
Solid Copper
Conductors
- 10 -
Battery
Connections
(non power-limited)
Correct Wire
Handling
External
Jacketed
Shield
Wire
Pull back
external jacketed
shield approx. 1/2".
Supervisory Connections
(power-limited)
Optional
UL Listed
Battery
Enclosure
(non power-
limited)
eFlowNA8D Series Installation Guide