Warnings and Alarms

5 Warnings and Alarms
Fault
Alarm/
number
warning bit
number
2
5
5
4
7
8
9
10
11
13
14
16
17
24
30
31
32
38
44
46
47
50
51
52
53
54
55
56
36
Fault text
Warning
16
Live zero error
14
Mains ph. loss
11
DC over volt
10
DC under volt
9
Inverter overload
8
Motor ETR over
7
Motor th over
5
Over Current
2
Earth Fault
12
Short Circuit
4
Ctrl. word TO
50
Fan Fault
19
U phase loss
20
V phase loss
21
W phase loss
17
Internal fault
28
Earth Fault
Control Voltage
33
Fault
23
24 V supply low
AMA calibration
failed
15
AMA Unom,Inom
AMA low Inom
AMA big motor
AMA small mot
AMA par. range
AMA user
interrupt
Alarm
Trip
Cause of problem
locked
The signal on terminal 53 or 54 is less than 50% of the value
set in parameter 6-10 Terminal 53 Low Voltage,
parameter 6-12 Terminal 53 Low Current,
X
X
parameter 6-20 Terminal 54 Low Voltage, or
parameter 6-22 Terminal 54 Low Current. See also parameter
group 6-0* Analog I/O Mode.
Missing phase on the supply side or too high voltage
X
X
X
imbalance. Check the supply voltage. See
parameter 14-12 Response to Mains Imbalance.
X
X
DC-link voltage exceeds the limit.
X
X
DC-link voltage drops below voltage warning low-limit.
X
X
More than 100% load for a long time.
The motor is too hot due to more than 100% load for a long
X
X
time. See parameter 1-90 Motor Thermal Protection.
Thermistor or thermistor connection is disconnected. See
X
X
parameter 1-90 Motor Thermal Protection.
X
X
X
Inverter peak current limit is exceeded.
X
X
Discharge from output phases to ground.
X
X
Short circuit in motor or on motor terminals.
No communication to frequency converter. See parameter
X
X
group 8-0* General Settings.
The heat sink cooling fan is not working (only on 400 V, 30–
X
X
90 kW units).
Motor phase U is missing. Check the phase. See
X
X
parameter 4-58 Missing Motor Phase Function.
Motor phase V is missing. Check the phase. See
X
X
parameter 4-58 Missing Motor Phase Function.
Motor phase W is missing. Check the phase. See
X
X
parameter 4-58 Missing Motor Phase Function.
X
X
Contact the local Trane supplier.
Discharge from output phases to ground, using the value of
X
X
parameter 15-31 InternalFaultReason if possible.
X
X
Control voltage is low. Contact the local Trane supplier.
X
X
X
24 V DC supply may be overloaded.
X
Contact the local Trane supplier.
The setting of motor voltage, motor current, and motor
X
power is wrong. Check the settings.
X
The motor current is too low. Check the settings.
X
The motor is too big to perform AMA.
X
The motor is too small to perform AMA.
The parameter values found from the motor are outside the
X
acceptable range.
X
The AMA has been interrupted by the user.