Extended Status Words; List Of Warnings And Alarms - Trane TR150 Programming Manual

Hide thumbs Also See for TR150:
Table of Contents

Advertisement

Troubleshooting

4.4 Extended Status Words

Bit
Hex
0
1
1
2
2
4
4
4
3
8
4
10
5
20
6
40
7
80
8
100
9
200
10
400
11
800
12
1000
13
2000
14
4000
15
8000
16
10000
17
20000
18
40000
19
80000
20
100000
21
200000
22
400000
23
800000
24
1000000
25
2000000
26
4000000
27
8000000
28
10000000
29
20000000
30
40000000
31
80000000
84
TR150 Programming Guide
16-94 Ext.
16-95 Ext. Status
Dec
Status Word
1
Ramping
2
AMA running
4
Start CW/CCW
8
0
16
0
Feedback
32
high
64
Feedback low
Output
128
current high
Control Ready
Output
256
current low
Drive Ready
Output
frequency
512
high
Output
1024
frequency low
2048
0
4096
0
Freeze Output
8192
Braking
16384
0
Freeze Output
32768
OVC active
Jog Request
65536
AC brake
131072
0
Start request
262144
0
Reference
524288
high
1048576
Reference low
Local Ref./
2097152
Remote Ref.
4194304
0
Sleep boost
8388608
0
16777216
0
33554432
0
67108864
0
External Interlock
Firemodelimi-
134217728
0
268435456
0
FlyStart Active
536870912
0
1073741824
0
Database
2147483648
busy

4.5 List of Warnings and Alarms

WARNING
Word 2
Hazardous Service Procedures!
Off
The maintenance and troubleshooting procedures
Hand/Auto
recommended in this section of the manual could result
0
in exposure to electrical, mechanical or other potential
0
safety hazards. Always refer to the safety warnings
0
provided throughout this manual concerning these
procedures. Unless specified otherwise, disconnect all
0
electrical power including remote disconnect and
0
discharge all energy storing devices such as capacitors
before servicing. Follow proper lockout/tagout
procedures to ensure the power can not be inadvertently
energized. When necessary to work with live electrical
components, have a qualified licensed electrician or
other individual who has been trained in handling live
electrical components perform these tasks. Failure to
Quick Stop
follow all of the recommended safety warnings provided,
could result in death or serious injury.
DC Brake
Stop
WARNING/ALARM 2, Live zero error
0
This warning or alarm will only appear if programmed by
the user in 6-01 Live Zero Timeout Function. The signal on
Request
one of the analog inputs is less than 50% of the minimum
value programmed for that input. This condition can be
caused by broken wiring or faulty device sending the
signal.
Jog
WARNING/ALARM 4, Mains phase loss
Start
A phase is missing on the supply side, or the mains
voltage imbalance is too high. This message also appears
0
for a fault in the input rectifier on the frequency converter.
Start Delay
Options are programmed at 14-12 Function at Mains
Imbalance.
Sleep
CAUTION
Live Electrical Components!
Running
Bypass
Troubleshooting:
Fire Mode
Check the supply voltage and supply currents to
the frequency converter.
texceed
WARNING/ALARM 7, DC overvoltage
If the intermediate circuit voltage exceeds the limit, the
0
frequency converter trips after a time.
0
Troubleshooting:
Extend the ramp time
0
Activate functions in 2-10 Brake Function
WARNING/ALARM 8, DC under voltage
If the intermediate circuit voltage (DC) drops below the
under voltage limit, the frequency converter trips after a
fixed time delay. The time delay varies with unit size.
BAS-SVP16A-EN - Rev. 2013-09-05