Programming
Parameter
Parameter 3-02 Minimum
Reference
Parameter 3-03 Maximum
Reference
Parameter 3-10 Preset Reference -100–100%
Parameter 3-41 Ramp 1 Ramp
Up Time
Parameter 3-42 Ramp 1 Ramp
Down Time
Parameter 4-12 Motor Speed
Low Limit [Hz]
Parameter 4-14 Motor Speed
High Limit [Hz]
Parameter 4-19 Max Output
Frequency
Parameter 6-20 Terminal 54 Low
Voltage
Parameter 6-21 Terminal 54
High Voltage
Parameter 6-22 Terminal 54 Low
Current
Parameter 6-23 Terminal 54
High Current
Parameter 6-24 Terminal 54 Low
Ref./Feedb. Value
Parameter 6-25 Terminal 54
High Ref./Feedb. Value
Parameter 6-26 Terminal 54
Filter Time Constant
Parameter 6-29 Terminal 54
mode
Parameter 20-81 PI Normal/
Inverse Control
Parameter 20-83 PI Start Speed
[Hz]
Parameter 20-93 PI Proportional
Gain
Parameter 20-94 PI Integral
Time
Parameter 30-22 Locked Rotor
Protection
BAS-SVX58D-EN
TR150 and TR170 Quick Guide
Range
Default
-4999.000–4999.000
0
-4999.000–4999.000
50
0
0.05–3600.0 s
Size related
0.05–3600.0 s
Size related
0.0–400.0 Hz
0.0 Hz
0.0–400.0 Hz
100 Hz
0.0–400.0 Hz
100 Hz
0.00–10.00 V
0.07 V
0.00–10.00 V
10.00 V
0.00–20.00 mA
4.00 mA
0.00–20.00 mA
20.00 mA
-4999–4999
0
-4999–4999
50
0.00–10.00 s
0.01
[0] Current
[1] Voltage
[1] Voltage
[0] Normal
[0] Normal
[1] Inverse
0–200 Hz
0 Hz
0.00–10.00
0.01
0.1–999.0 s
999.0 s
[0] Off
[0] Off
[1] On
08/2020 All rights reserved.
Usage
The minimum reference is the lowest value obtainable by
summing all references.
The maximum reference is the highest value obtainable by
summing all references.
Enter the setpoint.
Ramp-up time from 0 to rated parameter 1-23 Motor
Frequency for asynchronous motors. Ramp-up time from 0
to parameter 1-25 Motor Nominal Speed for PM motors.
Ramp-down time from rated parameter 1-23 Motor
Frequency to 0 for asynchronous motors. Ramp-down time
from parameter 1-25 Motor Nominal Speed to 0 for PM
motors.
Enter the minimum limit for low speed.
Enter the maximum limit for high speed.
Enter the maximum output frequency value. If
parameter 4-19 Max Output Frequency is set lower than
parameter 4-14 Motor Speed High Limit [Hz],
parameter 4-14 Motor Speed High Limit [Hz] is set equal to
parameter 4-19 Max Output Frequency automatically.
Enter the voltage that corresponds to the low reference
value.
Enter the voltage that corresponds to the high reference
value.
Enter the current that corresponds to the low reference
value.
Enter the current that corresponds to the high reference
value.
Enter the feedback value that corresponds to the voltage
or current set in parameter 6-20 Terminal 54 Low Voltage/
parameter 6-22 Terminal 54 Low Current.
Enter the feedback value that corresponds to the voltage
or current set in parameter 6-21 Terminal 54 High Voltage/
parameter 6-23 Terminal 54 High Current.
Enter the filter time constant.
Select if terminal 54 is used for current or voltage input.
Select [0] Normal to set the process control to increase the
output speed when the process error is positive. Select [1]
Inverse to reduce the output speed.
Enter the motor speed to be attained as a start signal for
commencement of PI control.
Enter the process controller proportional gain. Quick
control is obtained at high amplification. However, if
amplification is too high, the process may become
unstable.
Enter the process controller integral time. Obtain quick
control through a short integral time, though if the
integral time is too short, the process becomes unstable.
An excessively long integral time disables the integral
action.
4
4
29