Programming
Parameter
Parameter 4-12 Motor Speed
Low Limit [Hz]
Parameter 4-14 Motor Speed
High Limit [Hz]
Parameter 4-19 Max Output
Frequency
Parameter 30-22 Locked Rotor
Protection
Parameter 30-23 Locked Rotor
Detection Time [s]
Table 4.6 Motor Set-up Wizard Settings
Changes made
The changes made function lists all parameters changed
from default settings.
•
The list shows only parameters that have been
changed in the current edit set-up.
•
Parameters that have been reset to default values
are not listed.
•
The message Empty indicates that no parameters
have been changed.
Changing parameter settings
1.
To enter the Quick Menu, press the [Menu] key
until the indicator in the display is placed above
Quick Menu.
▲
▼
2.
Press [
] [
] to select the wizard, closed-loop set-
up, motor set-up, or changes made.
3.
Press [OK].
▲
▼
4.
Press [
] [
] to browse through the parameters in
the Quick Menu.
5.
Press [OK] to select a parameter.
▲
▼
6.
Press [
] [
] to change the value of a parameter
setting.
7.
Press [OK] to accept the change.
8.
Press either [Back] twice to enter Status, or press
[Menu] once to enter the Main Menu.
BAS-SVX58D-EN
TR150 and TR170 Quick Guide
Range
Default
0.0–400.0 Hz
0.0 Hz
0.0–400.0 Hz
100.0 Hz
0.0–400.0 Hz
100.0 Hz
[0] Off
[0] Off
[1] On
0.05–1.00 s
0.10 s
08/2020 All rights reserved.
Usage
Enter the minimum limit for low speed.
Enter the maximum limit for high speed.
Enter the maximum output frequency value. If
parameter 4-19 Max Output Frequency is set lower than
parameter 4-14 Motor Speed High Limit [Hz],
parameter 4-14 Motor Speed High Limit [Hz] is set equal to
parameter 4-19 Max Output Frequency automatically.
–
–
The main menu accesses all parameters
1.
Press the [Menu] key until the indicator in the
display is placed above Main Menu.
▲
▼
2.
Press [
] [
] to browse through the parameter
groups.
3.
Press [OK] to select a parameter group.
▲
▼
4.
Press [
] [
] to browse through the parameters in
the specific group.
5.
Press [OK] to select the parameter.
▲
▼
6.
Press [
] [
] to set/change the parameter value.
7.
Press [OK] to accept the change.
4.3 Parameter List